DC link adapter
10.5 Installation
10.5
Installation
Required tools:
• Slot-head screwdriver (1 x 5.5) for releasing the protective cover
• Torx screwdriver T20 for DC link screws (Torx slot)
Table 10-2
Installation of the DC link adapter at the HF Damping Module
1 x 5,5
1. Release and open the protective cover of the DC link.
3. Fix the DC link adapter (1.8 Nm) using the previously re‐
moved DC link screws. Use the right-hand holes
Electric shock when touching the DC link busbars
Contact with live parts can result in death or serious injury.
• Mount the busbars and clips of the DC link as well as the DC link adapter, so that after closing
150
①
WARNING
the DC link cover they cannot be touched.
2. Remove the DC link screws.
4. Remove the DC link side cover and close the protective cover
.
until you hear it engage.
High Frequency Drive
System Manual, 10/2020, 6SL3097-5AH10-0BP0