Table 35 AUTO_TUNE_RESULT & TRAVEL_CALIB_RESULT (Continued)
Value
Comment
50% angle warning
62
100
Small angle span error
Large angle span error
101
50% angle error
102
Linear adjust error
103
Offset measurement failed
120
error
Gain measurement failed
121
error
Response speed
122
measurement failed error
Hysteresis measurement
123
failed error
255
In operation
(*1) Number 103 is not shown for AUTO_TUNE_RESULT. Number 1 through 44 and 120
through 123 are not shown for TRAVEL_CALIB_RESULT.
(*2) E stands for Error, and W stands for Warning.
Error
/Warning
(*2)
VALVE_TYPE is linear and the rotation angle at the 50%
W
position exceeds ±20°.
W
Rotation-angle span < 5°.
VALVE_TYPE is linear and the rotation-angle span exceeds
E
60°; or VALVE_TYPE is rotary and the rotation-angle span
exceeds 100°.
VALVE_TYPE is linear and the rotation angle at the 50%
E
position exceeds ±25°.
FINAL_VALUE.value falls outside 50 ±10% at 50%
E
position.
Offset measurement has failed.
E
Gain measurement has failed.
E
Response speed measurement has failed.
E
Hysteresis measurement has failed.
E
Auto tuning is being executed.
128