HUVF SERIES DUCT MOUNTED UV SYSTEM
Power Connection
M
F
M
F
Constructing Array Support
Structure
WARNING
Construction Collapse Hazard.
Can cause personal injury or equipment damage.
Provide adequate structural support to prevent
array collapse. Support each unit with external
structural elements across both top and bottom and
add cross supports, as needed.
Provide adequate array support to prevent collapse:
• Provide minimum of external structural support
across the top and bottom of each unit.
• Provide cross supports, as needed.
CROSS SUPPORTS
ATTACHED TO DUCT FLANGE
Fig. 6. Array support structure.
31-00455—01
M
M
F
M
M
F
Fig. 5. Array interconnections.
INSTALLATION
When Installing This Product...
AIR HANDLER
1. The UV system is designed only for use inside Air
DUCT FLANGE
2. The UV system must be installed inside the AHU or air
3. Proper PPE and UV eye protection to be used during
4. Testing of lamps other than once installed inside an
M13457
5. The installation, service and maintenance of the sys-
4
WARNING
UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.
Do not look at the UV lamp when lighting is on. Use
indicator light on the ballast to check status. In
order to prevent exposure to UV light, before repair
of any parts of HVAC system, shut off power supply
to UV system. Do not install in a position where UV
lamp is visible during normal operation of HVAC
equipment.
Handling Units (AHU) and Air ducts. The units must
not be used in any other location or manner. The
manufacturer will not be responsible for the perfor-
mance of the system or any hazard to health by its
use in an unintended manner.
duct. An interlock switch to turn off the UV system
should be provided during installation that turned off
the UV system in the event the AHU is opened or
accessed to prevent exposure to humans.
installation of the system, UV rays are harmful to the
human skin and eyes, care must be taken to ensure
no direct exposure.
AHU fitted with an interlock switch should only be
done inside custom built fully enclosed test equip-
ment.
tem must be carried out by the qualified personnel of
authorized representative.
To adjacent unit
M
M