Parameter Settings; Contents Of This Chapter; Drive Parameter Settings - ABB ACS880-07 User Manual

Emergency stop, stop category 1 (option+q964) for
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Parameter settings

Contents of this chapter

This chapter contains the parameter settings related to the safety function.

Drive parameter settings

This section shows the drive parameter settings related to the safety function in the ACS880
primary control program.
The table that follows shows the parameters that are set at the factory.
No.
Name
14.01
Module 1 type
14.02
Module 1 loca-
tion
14.09
DIO 1 function
14.14
DIO 2 function
14.34
RO1 source
21.04
Emergency
stop mode
21.05
Emergency
stop source
31.03
External event
2 source
31.04
External event
2 type
1)
Description
Default value
FIO-01
Activates (and specifies the type of) I/O extension module
1.
Slot 1
Specifies the slot (1...3) on the control unit of the drive into
which the I/O extension module is installed.
Input
Selects whether DIO1 of the extension module is used as a
digital input or output.
Input
Selects whether DIO2 of the extension module is used as a
digital input or output.
P.14.5.1-
Selects a drive signal to be connected to relay output RO1.
In this case, the RO1 is energized by the status of DIO2 of
the FIO module (inverted value).
Eme ramp stop (Off3)
Selects the way the motor is stopped when an emergency
stop command is received.
P.14.5.1
Selects the source of the emergency stop signal. In this case,
the source is DIO2 of the FIO module.
P.14.5.0
Selects the source of external event 1. In this case, the
source is DIO1 of the FIO module.
Warning/Fault
Selects the type of external event 2.
Parameter settings 19