13.11 Outdoor Fan Motor Control

When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
This is to release the heat and to obtain the lowest pressure as fast as possible.

13.12 Hot Start Control

Hot start control is to prevent cool air discharge into room when heating operating starts.
Hot start is executed after heating operation starts and deice operation is completed.
Indoor fan control during hot start is shown below:
When indoor pipe temperature over 34°C or maximum 240 seconds, hot start is completed.
During hot start and for 30 seconds after hot start completed, intake thermostat is ignored and no Thermo OFF.

13.13 Cold Draft Prevention Control

This operation is to prevent the Cold Draft during Heating mode operation.
The operation will start when compressor OFF (Thermo OFF) during Heating operation.
For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor
heat exchanger temperature as shown below:
After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
Anti Cold Draft Control will stop when:
Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)
o
30 Minutes Time Save Control activates.
o
Indoor Pipe Temperature
≤ 30°C
30°C < t ≤ 34°C
t ≥ 34°C
Indoor Fan
OFF
SLo
Lo-
81