INSTALLATION
When Installing This Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service tech-
nician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Electric Shock Hazard.
Can cause electrical shock or equipment damage.
Do not connect to power before installation is
complete.
Assemble Conduit Framework
1. Measure and cut tubing to length then slide on con-
duit/lamp clamps (Fig. 5.), do not fully tighten bolts
yet.
Fig. 5. Slide on Hardware.
2. Use self-tapping screws to attach L-brackets to the
air handler wall or supporting structure. Then use the
½ inch pip clamps to attach the tubing sections to
the L-Brackets. (Fig. 6.)
Fig. 6. Mount L-bracket and Tubing.
3. An optional vertical support adds strength to the
conduit tubing to support framework and prevents
sagging on installations with three or more lamps per
Install UV Lamps
Snap UV Lamps into the lamp/conduit clamps. Be sure to
clamp to the rubber lamp connector on one end and the
ceramic lamp tip on the other end. DO NOT clamp onto the
lamp glass. Use black nylon zip-ties to secure lamp cables
to tubular rack components and/or supports.
Conduit
Broken Bulb Cleanup
Do not use a household vacuum. Sweep debris into a
plastic bag and dispose of properly.
Contact your local waste management authority for
instructions regarding recycling and the proper disposal of
old bulb(s).
5
UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS
tubing length. Measure the distance from floor to
ceiling then measure and cut tubing 1.75 inches less
than that length. Use ½ inch pipe coupling to extend
the vertical support to the floor and ceiling for a snug
fit. (Fig. 7.)
Conduit/
conduit
Clamp
Vertical Support
1/2" Pipe Coupling
Fig. 7. Optional Vertical Support.
CAUTION
Breakable Glass Hazard.
Can cause personal injury.
Be careful when inserting bulb(s) into lamp base.
Wear protective gloves when handling bulb(s).
MERCURY NOTICE
This device contains mercury in the sealed
ultraviolet bulb(s). Do not place your used bulb(s) in
the trash. Dispose of properly.
1/2" Pipe Coupling