INSTALLATION AND MAINTENANCE INSTRUCTIONS
W-MMF Wireless Monitor Module
SPECIFICATIONS
Maximum Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Maximum IDC Wiring Resistance:
Maximum IDC Voltage:
Maximum Average IDC Current:
Maximum Transmit RF Power:
Radio Frequency Range:
Temperature Range:
Humidity:
Battery Type:
Battery Life:
Battery Replacement:
Dimensions:
Accessories:
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the con-
trol panel installation manual and the SLC Wireless Gateway Manual for detailed
system information. If the modules will be installed in an existing operational system,
inform the operator and local authority that the system will be temporarily out of ser-
vice. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The W-MMF Monitor Module is intended for use with a wireless gateway or wire-
less fire alarm control panel (FACP) to interface with a device having contacts used
to signal status conditions. The input to the monitor module is non-latching and does
not require a reset. The device communicates through a robust, bi-directional mesh
network to the gateway and/or FACP. Rotary decade switches are provided for setting
the module's address. The module has a panel controlled LED indicator. (Figure 1)
FIGURE 1. CONTROLS AND INDICATORS:
FACEPLATE
The faceplate includes a magnet for activation and tamper resistance (Figure 2). The
faceplate magnet activates communication to the panel, therefore, the faceplate must
be installed for the module to work properly. The magnet also activates a supervisory
tamper fault at the panel if the nameplate is removed. Do NOT remove this magnet.
The faceplate for a wireless module CANNOT be replaced with the faceplate of a
standard wired module.
FL-450-000
September 8, 2015
3.3 VDC
5.0 mA (LED on)
210 µA, 3.9k EOL
3.9K Ohms
10 Ohms
3.2 Volts
5.5 µA
17 dBm
902-928 MHz
32°F to 120°F (0°C to 49°C)
10% to 93% Non-condensing
4 Panasonic CR123A or 4 Duracell DL123A
2 year minimum
Upon TROUBLE BATTERY LOW display and/or during annual maintenance
4¼ in. H x 4¼ in. W x 1½ in. D
SMB500 Electrical Box (preferred mounting option)
C1095C-00
FIGURE 2. FACEPLATE INTERIOR:
BATTERY REPLACEMENT
Low battery levels on the wireless devices are displayed as a trouble in an annun-
ciator. Therefore when the message "TROUBLE BATTERY LOW" is displayed, re-
place the battery in the device. This message is an indication that approximately one
week of battery life remains.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible Fire-Lite
system control panel (list available from Fire-Lite).
To replace the batteries in a wireless device use the following steps:
1. Have 4 CR123A (or DL123A) batteries available
2. Remove the faceplate from the module.
3. Open the battery compartment refer to Figure 3.
4. Remove the used batteries and replace with new batteries. The battery compart-
ment is designed such that the batteries can only align in the appropriate direction.
Do not force the batteries into the openings.
5. Replace the battery compartment cover.
6. Replace the faceplace.
1
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
MAGNET LOCATION
(DO NOT REMOVE)
C1098-00
I56-4083-003

Advertisement

loading

Summary of Contents for Honeywell W-MMF

  • Page 1 NOTICE: This manual should be left with the owner/user of this equipment. GENERAL DESCRIPTION The W-MMF Monitor Module is intended for use with a wireless gateway or wire- less fire alarm control panel (FACP) to interface with a device having contacts used to signal status conditions.
  • Page 2 COMPARTMENT C2002-00 MOUNTING C1097-00 The W-MMF mounts directly to an SMB500 electrical box (see Figure 4). To avoid interference with the wireless network metal electrical boxes are NOT recommended. Non-metal surface mounted electrical boxes (SMB500) are available from Fire-Lite. C1096-00 If not using an SMB500, the minimum mounting opening dimensions for the W- MMF are 4 in.