9.3

Environmental conditions

The temperature values were checked in accordance with IEC 60068-2-1, IEC 60068-2-2, and
IEC 60068-2-14.
You will find the permissible mounting positions in Permissible mounting positions (Page 22).
Operation
Storage / shipping
Gradient
Relative humidity
Air pressure
* BIOS power switch on "High Temperature" and USB load max. 1 W.
Vibration resistance
Operation
Storage / shipping
Shock resistance
Operation
Storage / shipping
7KN POWERCENTER 3000
Equipment Manual, 07/2020, L1V30579222003-03
Operation
Storage / shipping
Operation / storage / transport
Standard rail mounting (interfaces above / below)
0 °C to 50 °C / 55 °C (32 °F to 122 °F / 131 °F) *
-20 ... +60 °C (-4 to 140 °F)
Operation: Max. 10 ° / h (18 °F / h)
Storage: 20 °C / h (36 °F / h), no condensation
Tested according to IEC 60068-2-78, IEC 60068-2-30
5 ... 85 % at 30 °C (86 °F), no condensation
5 ... 95 % at 25 / 55 °C (77 / 131 °F), no condensation
1080 ... 660 hPa (15.7 ... 9.6 psi), corresponds to a height of
–1000 ... 3500 m (3280 ... 11,500 ft.)
Tested in accordance with IEC 60068-2-6
With DIN rail:
10 ... 58 Hz: 0.0375 mm (.0015 in.)
58 ... 200 Hz: 4.9 m / s² (.5 g)
5 ... 9 Hz: 3.5 mm (0.14 in.)
9 ... 500 Hz: 9.8 m / s² (1 g)
Tested according to IEC 60068-2-27
150 m / s² (15 g), 11 ms
250 m / s² (25.5 g), 6 ms