5.2.
Parameter Overview Standard Software (HART-Protocol see Page 33) and Data Entry
Submenu/Parameter
* Prog. Protection*
on
Prog. Protection
Language
English
Submenu
Primary
RangeMax
10 m/s
1800.00
m3/h
Qmax
400.00
m3/h
Entry Type
from table/numeric
* Prog. Protection*
ENTER
off
PP-Code
0
Prog. Protection
off
numeric
Old PP-Code?
ENTER
0
Prog. Protection
from table
from table
Meter size
ENTER
250 mm
Primary
10DS2110/3110
numeric
Electromagnetic Flowmeter Converter
Data can only be entered when the program protection has been
turned off.
on / off
If a value other than "0" (factory default setting) has been selected
for the Prog. Prot. Code, then the program
protection can only be turned off after the correct
PP-Code (1–255) has been entered.
After the program protection has been turned off, parameters can
be changed.
After the program protection has been turned off, it is also
possible to change the PP-Code.
Enter the old PP-Code.
0 = Factory default setting
Enter the new PP-Code (0–255)
German, English, French, Finnish, Spanish,
Italian, Dutch, Danish or Swedish can be
selected as the language for the display.
Exit the submenu
C/CE
Installed flowmeter primary size, see Instrument Tag.
1/25" - 96" [DN 1 – DN 2400].
Select with arrow keys. Displayed in mm and inches.
10 in
When the size changes, Q
The pulse factor is set 1.
The short Model Number for the flowmeter primary:
10DS2110/3110/DS21/DS41/DS41 > 14" [DN 300]/DH
10DI1425 <20" [DN 500]
10DI1425 >16" [DN 400]
10DS3111 E >12" [DN 300]
10D1462/1472
10D1422
Switch S901on the connection board must be set for the
specific Model Type.
Automatic setting based on the flowmeter primary size
selection
Flow range end value for forward and reverse flow directions
Min. flow range setting 0–0.5 m/s
Max.flow range setting 0–15 m/s.
Flow range end value can be set between 0.5 and 15 m/s.
⋅
=
0,05 Ran ge
Comments
is automatically set to 10 m/s.
max
⋅
to
1,5 R ange
ma x
m ax
19