Switch Groups; Input Switch Group Iswgapc - ABB Relion Applications Manual

Voltage protection and control
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 3
REU611 standardized configuration
3.2
3.2.1
26
Function
Frequency measurement
Other
Input switch group
Output switch group
Selector
Minimum pulse timer (2 pcs)
Move (8 pcs)
1, 2, ... = Number of included instances. The instances of a protection function represent the number of
identical protection function blocks available in the standardized configuration.
() = optional

Switch groups

The default application configurations cover the most common application cases,
however, changes can be made according to specific needs through LHMI, WHMI
and PCM600.
Programming is easily implemented with three switch group functions including input
switch group ISWGAPC, output switch group OSWGAPC and selector switch group
SELGAPC. Each switch group has several instances.
Connections of binary inputs to functions, GOOSE signals to functions, functions to
functions, functions to binary outputs and functions to LEDs have been preconnected
through corresponding switch groups.
The real connection logic and the application configuration can be modified by
changing the parameter values of the switch groups. It is also possible to modify the
real connection logic and the application configuration through the matrix view in the
signal configuration menu in the WHMI.

Input switch group ISWGAPC

The input switch group ISWGAPC has one input and a number of outputs. Every input
and output has a read-only description. ISWGAPC is used for connecting the input
signal to one or several outputs of the switch group. Each output can be set to be
connected or not connected with the input separately via the "OUT_x connection"
setting.
1MRS758335 B
IEC 61850
A
FMMXU
1
ISWGAPC
10
OSWGAPC
20
SELGAPC
6
TPGAPC
10
MVGAPC
1
REU611
Application Manual