Engine Oil Use Time Reset Method; O Perating The Fuel Gas Solenoid Valve Forced Off Switch - Sanyo W MULTI SGP-EW120M2G2W Manual

Gas heat pump air conditioner
Table of Contents

Advertisement

m Engine Oil Use Time Reset Method
Make sure to perform this procedure after checking (re-
plenishing, changing) the engine oil.
1) P ress the HOME (S004) key for one second or more.
The menu display will show item number "  "
2) N ext, press the UP (S005) and DOWN (S006) key,
displaying the menu item numbers. Go to menu item
"  "
3) A fter menu item number "  " appears, the oil
use time will be displayed. Press the SET (S007) key.
4) W hen the SET (S007) key is pressed with the oil use
time displayed (Figure 3), the next display appears. By
pressing the UP (S005) key or DOWN (S006) key in this mode, the oil use time display clear setting or the forced
oil replenishment setting can be selected. Select the setting to clear oil use time display ("  " on the
7-segment LED display).
↑DOWN
↓UP
5) Clearing the Oil Use Time Display
When the SET (S007) key is pressed for 1 second or
more while the oil use time display is selected,
"  " will appear on the 7-segment LED display
(Figure 4).
6) R elease the SET (S007) key once "  " is dis-
played, then quickly hold it down again. "  "
will be displayed (Figure 5), and the oil use time will
be reset to 0 hours. Next the oil use time will be dis-
played and can be checked.
Note: I f the oil use time does not return to 0 hours,
perform the procedure again.
n O perating the Fuel Gas Solenoid Valve Forced Off
Switch
This VG switch (S002) is used to forcibly close the gas
solenoid valve (Figure 6).
«This switch should normally be set to "NORMAL". »
Display


I - 5
Oil use time (10,100 hours)
"o" is displayed, indicating oil use time
Figure 3
Function
Oil use time display clear setting
Forcible oil replenishment setting
Figure 4
Figure 5
Figure 6

Advertisement

Table of Contents
loading

Table of Contents