Phone Supv Time; Alarm On Fail; Buzz On Fail; Two Phone Lines - Bosch D9412GV2 Program Entry Manual

Table of Contents

Advertisement

D9412GV2/D7412GV2 | Program Entry Guide | 2.0

Phone Supv Time

Default:
Blank
Selection:
Blank or 10 to 240
Blank
No phone line supervision.
10 to 240
Enter the number of seconds (in 10
second increments) you wish to
supervise the phone line. After a
faulted phone line restores, it takes the
same amount of time to start restoral
responses.
Phone line trouble responses: Keypads display
SERVC PH LINE # to indicate which phone line
failed. The keypad initiates a trouble tone if
Fail
is Yes and
CC Trouble Tone
With dual phone lines (using the D928 Module), the
restored phone line handles all messages regardless of
the phone line's number.
Phone, Trouble, and Restoral Events report when they
occur. They report also when a Diagnostic Report is
initiated from a keypad or by a Sked.

Alarm On Fail

Default:
No
Selection:
Yes or No
Yes
Generate alarm responses when a
phone line fails.
No
Phone failures report as trouble
responses for Area 1 or the account
number associated with Area 1.
Phone Supv Time must be programmed to
use this feature.
Phone Failure Alarm Responses: The Alarm Bell
relay for Area 1 activates. All Phone Event messages
report as Area 1 and the account number for Area 1.
Bosch Security Systems | 5/05 | F001U003636B
GV2MAIN

Buzz on Fail

Default:
Selection:
Yes
No
Buzz on
is Yes.
When
resulting trouble tone on individual keypads by setting
CC# Trouble Tone

Two Phone Lines

BFSK Duress Code

Default:
Selection:
If
Modem Format
program a number to identify Duress Reports at the
central station.
No
Yes or No
Generate panel-wide trouble tones and
display PHONE FAIL # at keypads
when a Phone Fail Event occurs.
Does not generate trouble tones at
keypads when a Phone Fail Event
occurs. PHONE FAIL # still displays.
Phone Supv Time must be programmed to
use this feature.
Buzz on Fail
is Yes, users can disable the
to No.
Default:
No
Selection:
Yes or No
Yes
The D928 Dual Phone Line Module
is installed. The LEDs on the D928
light to indicate primary or secondary
line trouble and COMM FAIL.
No
D928 Dual Phone Line Module is not
installed.
Program Phone Supv Time when using
two phone lines.
0
0 to 9
Duress Enable
in Area Parameters is Yes and
in Phone Parameters is No, you must
EN | 12