Communication
2.2 Modbus
2.2.7.3 Registers 0071 to 0088: Version Information (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: String
Table 2-7
Register
0071 to 0076
0077 to 0082
0083 to 0088
Unused positions in string are filled with character '\0'.
2.2.7.4 Registers 0101 and 0102: Device Status Indication (Read Only)
This register is write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Indication
Table 2-8
Register
0
0101/2
2
0101/2
4
0101/2
6
0101/2
8
0101/2
10
0101/2
12
0101/2
14
0101/2
0
0102/2
2
0102/2
to
14
0102/2
32
Registers 0071 to 0088: Version Information
Type of Information
Boot version
(string, max. 22 characters)
Firmware version
(string, max. 32 characters)
Parameter set version
(string, max. 32 characters)
Registers 0101 and 0102: Device Status
Type of Information
Device OK
Battery failure
SD card status
Reserved
Settings Load
Settings Check
Settings Activate
Reserved
Direction of rotation
Reserved
Remark
Example: V01.10.01
Example: V01.10.01
Example: V01.10.01
Remark
1 = Device ready for operation
0 = Battery OK,
1 = Battery failure (exchange battery)
1 = SD card error
(see notes in device manual, chapter 14,
Operational Indications)
= 0
1 = Parameter load is in progress
1 = Parameter check is in progress
1 = Parameter activation is in progress
= 0
0 = Anti-clockwise
1 = Clockwise
= 0
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020