Changing The Stop Category From 0 To 1 - ABB ACS880-07 User Manual

Emergency stop, configurable stop category 0 or 1 (option +q979)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Index
Name
200.202
SAR speed scaling
SARx.02
SAR initial allowed
range
SARx.21
SAR1 min ramp time
to zero
SARx.22
SAR1 max ramp time
to zero
SBC usage
SBC.15
SSE/SS1 SBC speed

Changing the stop category from 0 to 1

Stop category 0 is the default setting. This category uses the STO function of the FSO
module. Stop category 1 uses the SS1 function of the FSO module.
Example value
Description
1500 rpm
Sets a speed value that the FSO module
uses as a reference point in ramp parameter
calculations (see SAR1 ramp parameters
200.112, SARx.21, SARx.22 and SARx.02).
Adjust the default value when necessary.
100 ms
Sets the initial allowed range for the SARx
ramp. This parameter moves the location of
the maximum monitoring ramp forward on
the time axis, when monitoring is started.
The slope of the ramp stays the same as
defined with parameters 200.202 and
SARx.12 (SAR0) or SARx.22 (SAR1).
Time monitoring: This value has no effect
in the operation.
Ramp monitoring: Adjust the default value
according to the application requirements.
1000 ms
Sets the minimum ramp time for the SAR1
ramp monitoring.
Time monitoring: This value has no effect
in the operation.
Ramp monitoring: Sets the minimum decel-
eration time for the emergency stop. Adjust
the default value according to the application
requirements.
Note: With value 0 ms, the minimum ramp
is not monitored.
3000 ms
Sets the maximum ramp time for the SAR1
ramp monitoring.
Time monitoring: This value has no effect
in the operation.
Ramp monitoring: Sets the maximum decel-
eration time for the emergency stop. Adjust
the default value according to the application
requirements.
0 rpm
Sets the absolute speed below which the
FSO module activates the brake (SBC) while
ramping.
0 rpm: The feature is not in use.
In this manual, it is assumed that you do not
use a brake. If you do, you must take care
of its on/off control by the FSO module and
change this and other settings. See the FSO
module user's manual.
Parameter settings 41