Figure 4-14 - Flash Check In System Log - Siemens EN100 Installation And Activation

Firmware / fpga update via the ethernet interface
Table of Contents

Advertisement

Figure 4-14 - Flash check in system log

To launch new FGPA firmware you have to switch off the power supply for at least 20 seconds and switch it
on again. The device restart and activate the new FPGA – image which activates PRP.
NOTE: You may always repeat an upload of a file (EN100 or FPGA) before reboot on the device or EN100
firmware or power supply abruption.
The successful update can be checked with Netview
Page "RSTP1.htm" column "EPLD" -> Must be 555
for PRP
SCF 11/2008 V08.10
Or with module homepage
(http://<ip-address>/home e.g.)
Page "FEC-statistics"
Page 19 of 29