4.2
PS D75 .. .840 / PS DH30 ... 720 with built-in electronic overload protection
LED's
F1: (red)
Fault signal for Phase loss, Thyristor fault.
F2: (red)
Fault signal for Over temperature, Fault on circuit board, Thyristor fault,
High current switch off
On: (green) Supply voltage. Illuminates when softstarter has control power.
R: (yellow)
Motor is running. Illuminates when the motor is energised from the softstarter
T: (yellow)
Top of ramp. Start ramp is finished and stop ramp hasn't begun.
P: (yellow)
Energy saving is active
OVL: (yellow)
Fault codes
F1
Phase loss.
F2
Over temperature, Fault on circuit board, High current switch off
F1 + F2
Thyristor fault (short circuit or open circuit)
OVL
Overload
Relay Signals
Run / K4
Motor is running. The motor is energised from the softstarter
TOR / K5
Top of ramp. Start ramp is finished and stop ramp hasn't begun. Can be used as a by-
pass signal.
Fault / K6
Phase loss, Thyristor fault, Over temperature, High current switch off, Fault on circuit
board,
OVL / K3
Over load
Input
Start/Stop
Start when closed, stop when open, 24V, 20mA optocoupler differential input. +24V
and 0V can be supplied from the board if no external supply is used.
Reset
Reset of overload and short circuit detection. 24V, 20mA optocoupler input.
Run relay / K4
TOP relay / K5
Overload
U
START
60 sec.
STOP
- 16 -
time
<500 ms