Siemens SINAMICS G130 Operating Instructions Manual page 43

Dv/dt filter plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Table 6- 11
Technical specifications for the dv/dt filter plus Voltage Peak Limiter, 660 V – 690 V 3 AC, Part 4
Order number
Suitable for Power Module
Type rating of the Power
Module
I
thmax
Degree of protection
dV/dt reactor
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Connections
- to the Power Module
- load
- PE
Max. permissible cable
length between dV/dt reactor
and motor
Dimensions
Width
Height
Depth
Weight, approx.
Voltage Peak Limiter
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Connections
- to the dV/dt reactor
- DC
- PE
Dimensions
Width
Height
Depth
Weight, approx.
Two dV/dt reactors are required for these dV/dt filters. The technical data provided apply to one dv/dt reactor.
1)
Note
For versions with two dV/dt reactors, the cable lengths specified in the table do not change.
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 03/2012, A5E00692302A
6SL3000-
2DH38-1AA0
6SL3310-
1GH37-4AAx
kW
800
A
810
IP00
kW
0.828
kW
0.867
kW
0.927
2 x M12
2 x M12
M6
m
mm
445
mm
385
mm
312
kg
160
kW
0.106
kW
0.1
kW
0.091
M10
M10
M8
mm
309
mm
1312.5
mm
400
kg
72
1
300 (shielded)
450 (unshielded)
Technical specifications