4.2.4 Editing system information
Function: Edits system information of the module.
Operation: The following describes the operation procedure.
(1) In the Edit window (Figure 4-18), click the Edit system information button.
(2) The Edit system information window (Figure 4-19) appears.
- Setting a NET1 (NET2) refresh cycle
Set a refresh cycle for the I/O service. (If a sequence cycle is selected, the I/O service is refreshed in
synchronization with the sequence cycle.)
Do not set the refresh cycle to a duration shorter than the communication time calculated in section 6.2.
Setting range
- Setting the NET1 (NET2) status table
Set the starting address of the NET status table. Set the address listed in Table 4-3 NET status table
addresses that can be set, by using the PI/O register format.
Table 4-3 NET status table addresses that can be set
No.
1
X0000 to XFFFF
2
J000 to JFFF
3
Y0000 to YFFFF
4
Q0000 to QFFFF
5
G000 to GFFF
6
R000 to RFFF
7
M0000 to MFFFF
8
E0400 to EFFFF
9
LB0000 to LBFFFF
Figure 4-19 Edit system information window
3 to 3000
Address that can be set
PI/O register setting range
Unit: ms
Address setting range
H700000 to H71FFFE
H0A2000 to H0A3FFE
H700000 to H73FFFE
H740000 to H75FFFE
H0A8000 to H0A9FFE
H0AC000 to H0ADFFE
H760000 to H77FFFFE
H780800 to H79FFFE
H220000 to H23FFFE
4-21
4. Operation