Commissioning Cabinet Electronic Clasp Lock (For Fusionmodule800) - Huawei ECC800-Pro User Manual

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
----End
5.9 Commissioning Cabinet Electronic Clasp Lock (for
FusionModule800)
When the system type is FusionModule800 and the cabinet electronic clasp locks
are installed, perform the following steps to configure it.
Prerequisites
Procedure
Step 1 (Optional) Check whether the cabinet door lock is leveled to 2000 (+3) mm. If
not, adjust it.
Step 2 (Optional) If the cabinet door still cannot be opened after step 1 is performed,
adjust the position of the cabinet electronic clasp lock by using the slotted holes
until the cabinet door can be opened and closed properly.
Step 3 Set device addresses for cabinet electronic clasp locks.
Issue 02 (2020-09-07)
If the connection fails, check whether the cable is properly connected to
the device, whether the device is running properly, and whether the
parameter settings are consistent with the device parameters.
The cabinet electronic clasp locks of odd- and even-numbered cabinets have
been cascaded in hand-in-hand mode respectively. One end of a network
cable is connected to the RS485_IN port on the first cabinet electronic clasp
lock of an odd-numbered cabinet, and the other end of the cable is connected
to the COM2 port on the ECC800-Pro; one end of another network cable is
connected to the RS485_IN port on the first cabinet electronic clasp lock of an
even-numbered cabinet, and the other end of the cable is connected to the
COM3 port on the ECC800-Pro.
The smart module view has been deployed.
The cabinet door can be opened and closed properly. If the cabinet door
cannot be opened and closed properly, adjust the position of the cabinet
electronic clasp lock by performing steps 1 and 2.
A cabinet electronic clasp lock is installed at the front and rear doors of each
cabinet respectively. The address for the cabinet electronic clasp lock on the
front door is an odd number, and that for the cabinet electronic clasp lock on
the rear door is an even number.
The cabinet electronic clasp locks of odd-numbered cabinets are connected in
series. The addresses start from 1, and a maximum of 12 cabinet electronic
clasp locks can be connected in series.
The cabinet electronic clasp locks of even-numbered cabinets are connected
in series. The addresses start from 1, and a maximum of 12 cabinet electronic
clasp locks can be connected in series.
Set a device address for a cabinet electronic clasp lock by operating the DIP
switch on the cabinet electronic clasp lock. Toggle switches 1 to 6 specify the
device address in binary mode. ON indicates 1, and OFF indicates 0.
Copyright © Huawei Technologies Co., Ltd.