Connection Diagram - Honeywell 010690.02 Mounting And Connection Instructions

Mains/charger unit 12 v dc / 40 ah
Table of Contents

Advertisement

Available languages

Available languages

Mounting and Connection Instructions Mains/charger unit 12 V DC / 40 Ah
7.

Connection diagram

ST1
SE
S
S
+12 V DC
Output
0 V
Mains
Fault U_ext.
!U<
Test
U_bat <10.5 V
0 V
ST3
Accumulator 2
Accumulator 1
Ext. NTC
ST4
NTC1
When using an external
NTC, NTC1 must be
removed!
ON
Marked position:
All switches at ON
PO3
S1
LD 1
Accum. fault
1
<10.8 V
LD 2
2
LD 3
<10.5 V
U_bat
3
LD 4
<9.45 V
4
RESET
LD 5
Charging controller defective
5
LD 6
Mains missing
6
LD 7
7
Fault U_ext.
LD 8
8
SE aktive
1
Rel. 1
2
3
Rel. 2
X X
Si4
PO4
PO2
PO1
Charge
Si3
terminating
voltage
X
These potis (PO1, PO2, PO3)
may not be adjusted!
TR1
1
2
Si5
Si6
Si7
+ - + - + - + -
1
2
3
4
External user
4 x 12 V DC
X
TA1
Si1
Si2
ST2
N
L
N'
L'
Mains
230 V AC
External user
230 V AC
DIP switch S1
With S1, fault messages can be switched
through to the collective fault.
The respective switch must be at the
"ON" position.
S1/1
Mains fault
S1/2
Fault external user
S1/3
Charger controller defective
S1/4
Accumulator defective (<9.45 V)
LED Displays:
LD1
Accumulator fault
LD2
U_bat<10.8 V, switch-off warning
LD3
U_bat<10.5 V,
power supply switch-off
LD4
U_bat<9.45 V,
accumulator defective
LD5
Charger controller defective
LD6
Mains voltage missing
LD7
Fault external user
LD8
Fault input SE actuated
Potentiometer:
PO4
Charge terminating voltage
Fuses:
Si1
1 AT
Primary mains transformer
Si2
1 AT
External user 230 V AC
Si3
5 AT
Secondary mains transformer
Si4
2.5 AF
Output voltage 12 V DC
Si5
3.15 AF
Accumulator charging
Si6
1 AF
External user 12 V DC (1 and 2)
Si7
1 AF
External user 12 V DC (3 and 4)
7

Advertisement

Table of Contents
loading

Table of Contents