NEC FA Series User Manual page 13

Led wall bundle fine pitch led video display indoor
Hide thumbs Also See for FA Series:
Table of Contents

Advertisement

Caution!
Risk of overload of the power cable.
To protect the power cable against overload maximum 10 cabinets shall be
wired in a row at 100 V AC or 20 modules at 240 V AC. The total load must not
exceed 16 A per cable.
The limit values specified in the technical data must never be exceeded.
Only operate the system with supplied accessories (cables, power distribution, assist grip,
transport carts). However, a power cord to supply power is not included (see 3.1 Scope of
Delivery).
Do not operate or touch the system with wet hands.
Use the provided transition ramps (cable channels). Protect the cable against kinks and
sharp edges.
Notice
Use a TN-S power distribution system with a separate neutral and grounding conductor. Due
to voltage differences in the neutral conductor, large ground current loops can be avoided
therewith.
The complete electrical system should be protected by an appropriately rated disconnect
switch, circuit breakers, over voltage protector and Ground Fault Current Interrupters.
The power system needs to be installed according to the local electrical installation codes. For
Europe, installations have to be conform to DIN-EN 60364 – the standard for electrical
installation of buildings, (and related harmonized Norms). In Germany, the VDE 0100 should
be followed and adhered to.
Operational Range
© NEC Corporation 2019
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents