Installation
6.7.2.2 Connecting the water outflow to the safety valve
Combination Hydro-module H-Generation
For the combination hydro-module of the H-Generation, a safety valve (initial pressure 8 bar) is
integrated into the hot water tank. Safety valve and hot water tank have a common water outlet.
!
IMPORTANT
Also use the following instructions at the time of installation of the condensation outlet on the
combination hydro-module of the H-Generation:
● The outflow pipeline may be maximum 2 m long and have not more than 2 bends.
Carry out the following steps to connect the outflow line to the water outlet socket of the safety
valve of the combination hydro-module:
1. Use a connection of the size R ½ inches for installing the outflow line.
2. Lay the outflow line in a consistently downward alignment. The end of the outflow pipeline
must be visible and must not be near electrical components.
3. It is advisable to insert an outflow siphon in the outflow line, which is also visible and is
not in the vicinity of electrical components.
170
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
1 Water outlet socket of the
safety valve
1
Hydro-module H-Generation
Carry out the following steps to connect the outflow hose to the water outlet socket of the safety
valve of the hydro-module:
1. Slide the outflow hose onto the condensation outlet socket on the hydro-module.
2. Ensure that the outflow hose is seated firmly. Use a hose clip to attach the hose, if neces-
sary (to be provided on site).
3. Lay the outflow hose in a constant downward alignment into a suitable collection fixture
for the condensation (to be provided on site).
Detail view from below
1
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Installation
1 Water outlet socket of the
safety valve
171