This section describes the installation procedure of the PetaSite S-series Consolidated Storage
Management System including optional goods.
Follow the installation procedure described below as it includes the important safety information such as
prevention from falling.
4-1. Installation Space and Flow of Installation Procedure
4-1-1. Installation Space
The floor space to install this system requires the free space of at least 1000 mm to the front, 700 mm to
the rear, 10 mm to the right and 10 mm to the left of the outside panels of the console.
Free space of at least 700 mm above the system is also required.
Basic storage
system
10
CSM-200
Section 4
Installation
REAR
Extension
Extension
console
console
FRONT
10
(Unit : mm)
4-1