SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0
SP2
Industrial Controls
SIMOCODE DP
SIMOCODE DP PCS 7 Library
Migration (Legacy) - V9.0 SP2
Programming and Operating Manual
09/2019
A5E48307694002A/RS-AA/001
Introduction
SIMODIAG Function
SIMO_CHN Function
1
2
3

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMOCODE DP

  • Page 1 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 Introduction SIMODIAG Function Industrial Controls SIMO_CHN Function SIMOCODE DP SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual 09/2019 A5E48307694002A/RS-AA/001...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    3.1.15 Reset Response ........................20 3.1.16 Additional Functions........................ 20 3.1.17 Startup Response ........................20 3.1.18 Time-related Characteristics ....................20 3.1.19 Bumpless Changeover ......................20 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 4 SIMO_STAT Status Display ....................39 3.5.5 VSTATUS and VSTATUS1 Status Display ................40 Display in WinCC ........................41 3.6.1 Views ............................41 3.6.2 Status display ......................... 53 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 5: Introduction

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
  • Page 6: Product Specific Security Information

    PCS 7 to support a secure operation, such as: ● User rights ● Password protection of – WinCC – SIRIUS devices For more information, click here (https://support.industry.siemens.com/cs/document/60119725). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 7: Simodiag Function

    ● Inputs EN, RACKF, SUBN1ERR, SUBN2ERR and EN_DIAG are linked. 2.1.5 Startup response The "Startup" identifier (OMODE=16#xx00xxxx) is written to output OMODE in the OB100. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 8: Dp Master And Dp Slave Failure

    RACKF device failures are indicated by OB_DIAG1. The output of messages is enabled on input EN_MSG. 2.1.12 Operator control and monitoring There is no operator interface for the block. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 9: Inputs / Outputs

    1=Redundant DP Master system BOOL FALSE failure V1_LINK 1=Operation behind a Y-Link DPV1 BOOL FALSE Refer SIMODIAG Message Texts and Auxiliary Process Values (Page 10) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 10: Message Texts And Auxiliary Process Values

    Higher level error The input value of MODE is passed unchanged into the Low Word of OMODE. Refer SIMODIAG Function block Inputs / Outputs (Page 9). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 11: Simo_Chn Function

    Direct starter (DIR) Reversing starter (REV) Star-delta starter (STAR) Dahlander starter (DAHL) Pole changing starter (POL) Valve (VALVE) Positioner 1-5 (POS) Soft starter (SOFT) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 12: Project Configuration

    WinSIMOCODE-DP or SIMATIC PDM and not STEP 7. This blocking option disables the parameters being downloaded from the DP master and has to be set. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 13 Y-Link (47 x 5 slots = 235 slots, max. 236 slots). Also please refer to the information given in the Y-Link manual. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 14: Principle Of Operation

    SIMOCODE-DP device. 3.1.5 Principle of Operation In program file Blocks+Templates, the SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 provides templates for each control function. The control function dependent parameters, and the messages to appear on the faceplates, are preset with suitable values in the templates.
  • Page 15: Simulation

    REMON_OP is active. The required operator enabling signal QLOCOP is set by REM_SEL and enable signal LOCOP_EN. The active control station is output through QREMOTE (1=REMOTE, 0=LOCAL). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 16: Interlocking

    Positioner runs in CLOSED CLOSED VL_HOLD not active not active not active 1=STOP SS_POS not active not active 0=CLOSED 0=CLOSED (default) 1=OPEN (default) 1=OPEN SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 17: Manual / Automatic Operation

    The required operator enabling signal QMANLOP is set depending on MAN_SEL and enable signal MANLOPEN. The active setting is output through QMAN_MOP (1=MANUAL-LINKED; 0=MANUAL- OPERATOR). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 18: Monitoring Of Control Commands

    For controls from the OS, enable signal QENSDCS is also required. In this case, output QENSDCS is set depending on inputs SIMO_DPV1 and EN_SD_CS. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 19 If writing was not possible, output QERR_WSD is set. After the statistic data is read, or after a write error, inputs OPH_S, N_START_S, and N_OVL_S are set to the corresponding active values. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 20: Reset Response

    Consequently, operating inputs ON1_OP, OFF_OP, and ON2_OP do not have to be tracked. However, mode selections REMON_OP, AUTON_OP, and MANON_OP are always tracked in the active settings. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 21: Error Handling

    SIMO_OVL is a binary output, which is set if SIMOCODE is configured as overload (OVL). Refer AS block parameters in the CFC (Page 31). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 22: Inputs / Outputs

    (record 130) byte 9 BYTE 16#0 CS_UPD 0->1: update Diagnostic Data BOOL FALSE motor current in %Ie REAL CUR_AH HH Alarm LIMIT in %Is REAL 130.0 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 23 1=SIMOCODE - LOCKED BOOL FALSE LOCOP_EN ENABLE: 1=operator may input LOCAL BOOL TRUE M_SUP_C 1=Suppress current limit messages BOOL FALSE M_SUP_EXT 1=Suppress external Message BOOL FALSE SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 24 SIMOCODE DP 1.2: POS: status BOOL FALSE positioner run open; otherwise: not used Q1_3 SIMOCODE DP 1.3: POS: status BOOL FALSE positioner drive closed; otherwise: not used SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 25 SIMOCODE DP 0.4: lock time active BOOL FALSE QMAN_AUT 1=AUTO; 0=MANUAL BOOL FALSE QMAN_MOP 1=MANUAL-LINKED; BOOL FALSE 0=MANUALOPERATOR QMANLOP 1=operator enabled for input MANUAL BOOL FALSE LINKED/MANUAL OP SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 26 Remote 1=REMOTE; BOOL TRUE 0=LOCAL SIMOCODE RESET Operator Input: 1=Reset Monitoring Error BOOL FALSE RUNUPCYC Lag: Number of Run Up Cycles (>0) >0 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 27 16#4000: SIMOCODE DP 1.6, torque closed 16#8000: SIMOCODE DP 1.7, torque open SIM_I23 Simulated value motor current basic WORD 16#0 type 2 SIM_ON 1=activate simulation BOOL FALSE SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 28 DWORD 16#0 Refer SIMO_CHN Message Texts and Auxiliary Process Values (Page 29) Status display VSTATUS and VSTATUS1 (Page 40) Status display SIMO_STAT (Page 39) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 29: Message Texts And Auxiliary Process Values

    MSG_LOCK, Warning @4%d@/@5%d@ M_SUP_SMC QG_FLT $$BlockComment$$ General MSG_LOCK, Fault M_SUP_SMC @6%d@/@7%d@/@8%d@ QCST $$BlockComment$$ Test MSG_LOCK, (CST) M_SUP_SMC SETEXTMSG $$BlockComment$$ External MSG_LOCK, Signal @9%s@/@10%X@ M_SUP_EXT SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 30 EXTMSGVAL. Both of these are output as auxiliary process values with the message. Refer SIMO_CHN Function Block Inputs/Outputs (Page 11). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 31: As Block Parameters In The Cfc

    Command=ON2 Operating Hours X 10h OPH_S Operating Hours X 10h REMON_OP Operation=LOCAL Operation=REMOTE RESET Mon. Err=RESET SD_UPD StatData=Update SENSOR Sensor Value SIMORESET SIMO Fault=RESET SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 32 Parameter S7_string_0 S7_string_1 ON1_OP Command=not act. OFF_OP Command=OFF ON2_OP Command=ON QON1 not act. QOFF QON2 LOCK_OPT not act. SS_POS not act. not act. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 33 Assignment of AS block parameters contained in the CFC Template POL/DAHL to the I/O fields of the faceplate Parameter S7_string_0 S7_string_1 ON1_OP Command=SLOW OFF_OP Command=OFF ON2_OP Command=FAST QON1 SLOW QOFF QON2 FAST LOCK_OPT SLOW SS_POS not act. not act. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 34: Description Of Parameters

    1=Rev. 1=Slow OFF_OP not active not active 1=Off 1=Off 1=Off ON2_OP not active not active 1=On 1=Forw. 1=Fast SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 35 SIMOCODE-DP has elapsed (this is indicated on output QLTA and the Lock time active display in the Standard view. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 36: Inbt2 Assignment

    POS: Profibus-DP Byte 1 - DP Bit 1.3 Send -> [159] Status POS: Status run closed - run closed Q1_3 Otherwise: user-specific assignment Q1_4 user-specific assignment Q1_5 user-specific assignment Q1_6 user-specific assignment Q1_7 user-specific assignment SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 37 When using the CFC "Generate module driver" function, the MODE input is automatically linked to the OMODE output at block SIMODIAG or PADP_L00. Refer OBT2 assignment. (Page 38) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 38: Obt2 Assignment

    Fault response -> PLC-CPU Signal -> [063] DP Bit 0.7 Receive block as TRUE I1_0 user-specific assignment I1_7 2.0 - 3.7 I23 user-specific assignment Refer INBT2 assignment. (Page 36) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 39: Simo_Stat Status Display

    – 16#08: SOFT – 16#10: DIR – 16#20: REV – 16#30: STAR – 16#40: DAHL – 16#50: POL – 16#60: VALVE – 16#70: POS SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 40: Vstatus And Vstatus1 Status Display

    VSTATUS1 Bit_20:=not used; VSTATUS1 Bit_04:=QEM_START; VSTATUS1 Bit_19:=not used; VSTATUS1 Bit_03:=OverloadTest; VSTATUS1 Bit_18:=not used; VSTATUS1 Bit_02:=On2; VSTATUS1 Bit_17:=not used; VSTATUS1 Bit_01:=Off; VSTATUS1 Bit_16:=not used; VSTATUS1 Bit_00:=On1; SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 41: Display In Wincc

    SIMOCODE symbol into picture @Templates.PDL and use it for this configuration. ① Function symbol; Plant Hierarchy → Create / Update block icons ② Symbol for WinCC dynamic wizard SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 42 Overview window ① Tagname, Tooltip (#comment) ② Event state ③ Collect value ④ MSG_LOCK, QMSG_SUP ⑤ Occupied ⑥ Selection view ⑦ Selection group display SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 43 Active command (ON1_OP, ON2_OP, OFF_OP, QON1OP, QON2OP, QOFFOP) ④ LOCK ⑤ LOCK_ON ⑥ Lock option (LOCK_OPT; LOCK_OPT#string) ⑦ Reset of SIMOCODE-faults (SIMORESET) ⑧ Reset of QMON_ERR (RESET) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 44 @Level5 (Operator Enabling) -> Permissions (Operator Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 45 Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 46 (Operator Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 47 (Operator Enabling) -> Permissions (Operator Enabling). The operator enabling and background colors of the other I/O fields are then defined in picture element "Permissions" by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 48 Picture @CONL1_Standard.PDL is output. Motor current CUR is displayed as an online variable. No archiving is necessary. The settings can be changed on the picture symbol through the ReturnPath property. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 49 SIMO_CHN Function 3.6 Display in WinCC Alarms view SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 50 Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 51 Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 52 SIMO_CHN Function 3.6 Display in WinCC Batch view SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 53: Status Display

    8196 @Motor_is_forw.emf STAR 12288 @SimoMotorDefault.emf 12289 @Motor_error.emf 12290 @Motor_is_off.emf 12292 @SimoStar2.emf 12296 @SimoStar1.emf DAHL 16384 @SimoMotorDefault.emf 16385 @Motor_error.emf 16386 @Motor_is_off.emf 16388 @motor_is_on.emf 16392 @motor_is_slow.emf SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 54 24580 @vho_opened.emf 28672 @vho_undef.emf 28673 @VHO_error.emf 28674 @vho_undef.emf 28676 @vho_opened.emf 28680 @vho_closed.emf 28736 @vho_closed.emf (blink) 28800 @vho_opened.emf (blink) Note Settings with "-" are ignored. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 55 3.6 Display in WinCC Status display icons Icons Filename @MOTOR_Error.emf @motor_is_forw.emf @motor_is_off.emf @motor_is_on.emf @motor_is_rev.emf @motor_is_slow.emf @SimoMotorDefault.emf @SimoOvl1.emf @SimoOvl2.emf @SimoOvl3.emf @SimoStar1.emf @SimoStar2.emf @vho_closed.emf @VHO_Error.emf @vho_opened.emf @vho_undef.emf SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
  • Page 56 SIMO_CHN Function 3.6 Display in WinCC SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...