Siemens LMV5 Series Technical Instructions page 246

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diag.
Device
Display
Code
Code
0D
Invalid
57
parameterization
0E
58
Any #
59
Any #
Parameter Set
damaged
5A
Any #
5B
Any #
Parameter
5C
Any #
Backup Restore
LMV5
5D
Any #
Internal Fault
Basic Unit
5E
Any #
Parameter Set
5F
Any #
damaged
60
Any #
Any #
01
Internal Fault
02
Basic Unit
61
10
11
12
13
Section 7
Meaning for the LMV5x System
Fault with Base Unit (LMV5)
The redundancy contact monitoring function is not permitted
The COx function is not permitted.
Internal communication (µC1 <> µC2)
After initialization, EEPROM page is on ABORT
(last parameterization was possibly interrupted due to a power
failure)
Page number
CRC error of a parameter page
Page number
Page is on ABORT
Page number
Page is on WR_RESTO. A backup restore was made
Page number
Page open too long
Page number
Page has an undefined status
Page number
Last backup restore invalid (was interrupted)
Fault when copying a parameter page
Number of parameter page
Fault in connection with EEPROM initialization
Fault during initialization of EEPROM
Number of write attempts exceeded
EEPROM was busy when accessed
Comparison of EEPROM and RAM area revealed dissimilarity
Page area of EEPROM exceeded during write process
Access conflict µC1 <> µC2 (arbitration)
Page 38
HOME
Corrective Action
This function is only enabled for the LMV50 and
LMV52. Setting StartReleaseOil to "HT/FG-RedCo" is
not permitted.
This function is only enabled for the LMV50 and
LMV52. Changing OptgMode COx Gas(Oil) from
"deactivated" is not permitted.
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) Check for inductive loads on the outputs.
4) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
Reset the LMV5
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
4) If fault occurs continuously, replace LMV5.
Repeat parameter set download (from AZL to LMV5)
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
4) If fault occurs continuously, replace LMV5.
SCC Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents

Save PDF