Description
The Gamewell-FCI PID-95P addressable point identifica-
tion device is the interface between the non-powered, nor-
mally open, dry-contact devices and Gamewell-FCI's 600
Series and ILI95-E3 Series
Alarm Control Panels (FACPs). Point identification devices
monitor a single Style B circuit, and are designed for con-
cealed mounting in an electrical backbox. The PID-95P can
be surface or flush mounted and has a visible LED for
alarm/annunciation.
Operation
The point identification device connects to the Signaling
Line Circuit (SLC) via two wires. The PID-95 will monitor,
via a two-wire supervised SLC circuit, contact-type devices
such as a waterflow switch or a manual station. Upon acti-
vation of the monitored device, the PID-95 will report its
address to the 600 Series and ILI95-E3 Series FACP via
the analog SLC. The control panel will then activate into all
alarm programmed outputs related to the PID-95.
Programming
The PID-95 is programmed by setting a single DIP switch,
easily accessible on the device's printed circuit board. The
DIP switch sets the address of the device and the priority
interrupt (DIP SW #8). All other programming is accom-
plished at the FACP through a laptop computer or the con-
trol panel operator's display. (600 Series only).
Standard Application
The PID-95 is the interface between the dry-contact type
devices and the SLC of the control panel. The PID-95 is a
means of connecting and identifying monitor points without
the use of conventional input modules at the main control
panel. The use of PID-95s can dramatically reduce the field
wiring required on many projects.
E3 Series® is a registered trademark of Honeywell International Inc.
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.
®
of analog addressable Fire
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
Features
Compatible with the Gamewell-FCI, 600 Series and
ILI95-E3 Series Systems
Monitors dry-contact devices
Includes an LED for alarm annunciation
Field programmable
Provides priority interrupt
Offers a plate-mounted version available for surface or
flush mounting in a 4" x 4.688" (10.16 cm x 11.908 cm)
double gang backbox or 4" x (10.16 cm) square backbox
SIGNALING
GAMEWELL-FCI
PID-95P, PID-95
Point Identification Device
PID-95P
MEA
FM
Approved 7300-1703:0135
S521
APPROVED
CS-2044 Rev. C page 1 of 2
PID-95

Advertisement

loading

Summary of Contents for Honeywell PID-95P

  • Page 1 Fire Alarm Control Panels (FACPs). Point identification devices monitor a single Style B circuit, and are designed for con- cealed mounting in an electrical backbox. The PID-95P can be surface or flush mounted and has a visible LED for alarm/annunciation.
  • Page 2: Ordering Information

    4.688" (11.908 cm) plastic plate panel via the analog addressable circuit. The interface 70839 Trim ring for flush-mounting on the PID-95P device shall be Gamewell-FCI PID-95P or PID-95. Specifications PID-95P Standby Current: 0.0005A, 0.0008A...

This manual is also suitable for:

Pid-95