NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Figure 3-26 Water inlet and outlet pipes
(1) Condensate
drainpipe 1 (DN20)
Sealing
1.
2.
(1) Paper protective film
Issue 02 (2019-10-10)
(2) Condensate
drainpipe 2 (DN20)
Connect the water pipes using thread connectors. Connect external water inlet and outlet pipes using
connectors with inner screw threads.
When connecting water pipes, use appropriate active connectors and secure them using a wrench.
The drainpipe must be wrapped with thermal insulation foam (including the buried parts), and the
thickness of the thermal insulation foam is not less than 3 cm.
Remove the paper protective film from the sealing putty.
Seal the gap between the water pipe and the equipment using sealing putty after the pipe
is correctly connected.
Figure 3-27 Setting sealing putty
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
(3) Spray
(4) Spray water
drainpipe (DN40)
refill pipe (DN20)
(2) Sealing putty
43