Before You Begin Installing
EVS-RPU Remote Paging Unit
EVS-LOC Remote Command Unit
(includes 6860, RVM & SW-24)
EVS-100W 100W Amplifier
EVS-100WBU backup daughter card
A
Total System Current
Network Cards
SK-NIC Network Interface Card
SK-FML Fiber Optic Multi Mode
SK-FSL Fiber Optic Single Mode
Auxiliary Devices
IPDACT-2 IP Communicator
IPDACT-2UD IP Communicator
CELL-MOD/CELL-CAB-SK
B
Auxiliary Devices Current
Notification Appliance Circuits
5495/5499 Power Supply
C
Notification Appliances Current
D
Total current ratings of all devices in system (line A + line B + C)
E
Total current ratings converted to amperes (line D x .001):
F
Number of standby hours:
G
Multiply lines E and F.
H
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
I
Multiply lines E and H.
J
Add lines G and I.
1.
The FACP can only support 5 devices w/LED's on. This current draw has been added to the panels alarm current.
2.
If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
3.
If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that
time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be drawn
from the panel.
4.
Use next size battery with capacity greater than required.
5.
Total does not include isolator devices or accessory bases.
* Use a separate worksheet for each 5895XL.
14
Table 2.5 Current Draw Worksheet for SD SLC Devices
Device
# of Devices
(4 max.)
(4 max.)
(4 max.)
(4 max.)
(1 Max.)
(1 Max.)
(1 Max.)
3
Refer to devices manual for current rating.
(1 max.)
(1 max.)
Refer to device manual for current rating.
4
Calculating Current Draw and Standby Battery
Current per Device
Standby:
Alarm:
Standby:
Alarm:
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
Standby/Alarm:
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
24 VDC
One input circuit:
Both input circuits: 30 mA
Alarm:
Alarm:
Alarm:
Alarm:
Total standby AH
Total alarm AH
Total ampere hours
required
5895XL Manual - P/N 151142-L8:L 08/09/2017
Standby
Alarm
Current
Current
70 mA
mA
100 mA
100 mA
mA
150 mA
10 mA
mA
10 mA
mA
21 mA
mA
53 mA
mA
79 mA
mA
93 mA
mA
136 mA
98 mA
mA
155 mA
55 mA
mA
100 mA
mA
mA
mA
mA
mA
mA
mA
mA
15 mA
mA
mA
mA
mA
mA
A
H
AH
AH
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
H
AH