  • Page 1 ECO HEATING SYSTEM TDM PLUS HYDRO UNIT OUTDOOR UNIT Model : AE044MXTPEH AE090MNYDEH AE066MXTPEH AE090MNYDGH AE090MXTPEH AE160MNYDEH AE090MXTPGH AE160MNYDGH AE120MXTPEH AE120MXTPGH AE160MXTPEH AE160MXTPGH ECO HEATING SYSTEM CONTENTS 1. Precautions 2. General Overview 3. Disassembly and Reassembly 4. Troubleshooting 5. PCB Diagram 6.
  • Page 2: Table Of Contents

    1-6 Precautions for charging refrigerants ........................5 2. General Overview ..........................6 2-1 Features of the System ..............................6 2-1-1 Key features of the EHS(TDM PLUS) ......................7 2-1-2 Changes in comparison to basic model .....................8 2-1-3 Structure of product ............................10 2-2 Model names of Indoor/Outdoor Unit .......................11 2-2-1 Indoor Unit ................................11...
  • Page 3 Contents 4-4 Hydro Unit ..................................69 4-4-1 EEPROM error ..............................69 4-4-2 : Error due to abnormal data of Wired remote controller thermistor value ...70 4-4-3 Water pump & flow switch OFF ........................71 4-4-4 Water pump & flow switch ON ........................72 4-4-5 Hydro unit temperature sensor(open/short) ..................73 4-5-6 Communication error after finishing Tracking(Hydro unit) ............74 4-5 Items to check before diagnostics ........................75 4-5-1 Test run mode and view mode ......................
  • Page 4: Precautions

    Check whether the installation location is at least two meters away from other electronic products such as TV, video, or audio. – Otherwise, the video quality might be degraded or noise might be generated. Do not let end users repair the products themselves. – Unauthorized disassembly might cause electric shock or fire. Samsung Electronics...
  • Page 5: Precautions For The Safety

    – R410A is a quasi-azeotrope of two refrigerants. Make sure to charge liquid one when adding refrigerant. If you charge gaseous refrigerant, it may affect the capacity and reliability of the product as a result of change formation of the refrigerant. Samsung Electronics...
  • Page 6: Precautions For Handling A System Containing Refrigerants

    – The container may get damaged by the heat and result in explosions. Do not operate the product without pressure switch(for product protection) and sensor. – If there are any internal blockage, high refrigerant pressure increase may damage the product or exterior. Samsung Electronics...
  • Page 7: General Overview

    It has developed power saving compressors for more than thirty years. EHS(Eco Heating System) compressor adopts a double-rotor BLDC compressor with permanent magnets made by Samsung. Electricity for the compressor rotor is obtained from a neodium-iron-boron permanent magnetic material (boron magnet can attract iron material weighing 1000 times its own weight.) It strengthens the rotary moment of the compressor to maximize the entire efficiency of the...
  • Page 8: Key Features Of The Ehs(Tdm Plus)

    Floor heating is well known as the optimal heating option for indoor thermal comfort. However, it takes 4~8 hours to heat up the room after it is turned on. Samsung EHS TDM technology quickens that process by blow- ing hot air along with floor heating to warm up the room.
  • Page 9: Changes In Comparison To Basic Model

    AE090MXTP** Changed part Changed item and feature RD060/070/080PHX** AE090MXTPE* AE090MXTPG* Change Main PBA Main PBA - Non-NASA NASA Sub-display PBA Inverter PBA / Inverter PBA - Non-NASA NASA Change EMI PBA EMI PBA - Improves EMI characteristic. Reactor Samsung Electronics...
  • Page 10 General Overview AE120/160MXTP** Changed item and feature RD060/070/080PHX** AE120/160MXTPE* AE120/160MXTPG* Changed part Change Main PBA Main PBA - Non-NASA NASA Sub-display PBA Inverter PBA - Non-NASA NASA Change EMI PBA EMI PBA - Improves EMI characteristic. Reactor Samsung Electronics...
  • Page 11: Structure Of Product

    Control box Subcooler 4way valve Gas pipe for Hydro Gas pipe for Air Liquid pipe Compressor AE120/160MXTP** Heat exchanger Control box Subcooler 4way valve Accmulator Oil separator Gas pipe for Hydro Gas pipe for Air Liquid pipe Compressor Samsung Electronics...
  • Page 12: Model Names Of Indoor/Outdoor Unit

    EEV) Console 1. Make sure to use an indoor unit that is compatible with EHS TDM PLUS. 2. Indoor units can be connected within the range indicated in following table. 3. If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of the indoor unit may decrease.
  • Page 13: Combination And Connection Ratio Limitation

    (Not including Hydro-A2W) (kW) AE044MXTPEH 2.2~4.4 AE066MXTPEH 3.3~6.6 AE090MXTPEH 4.5~9.0 AE120MXTPEH 6.0~12.0 AE160MXTPEH 8.0~16.0 AE090MXTPGH 4.5~9.0 AE120MXTPGH 6.0~12.0 AE160MXTPGH 8.0~16.0 Available for max 7 indoor units. When considering the system capacity of allowable indoor units, follow the table above. Samsung Electronics...
  • Page 14: Components And Feature

    Model Fan motor Check valves (Inverter Rotary) Expansion Valve Sensor Sensor Switch valves AE044MXTPEH 4.4 1 x 95W AE066MXTPEH 6.6 1 x 95W AE090MXTP*H 9.0 1 x 125W AE120MXTP*H 12.0 2 x 125W AE160MXTP*H 16.0 2 x 125W Samsung Electronics...
  • Page 16: Product Specifications

    General Overview 2-5 Product Specifications (cont.) 2-5-2 Hydro Unit EHS TDM PLUS EHS TDM PLUS EHS TDM PLUS EHS TDM PLUS Type (HYDRO UNIT) (HYDRO UNIT) (HYDRO UNIT) (HYDRO UNIT) Model Name AE090MNYDEH/EU AE090MNYDGH/EU AE160MNYDEH/EU AE160MNYDGH/EU Mode Heat Pump (A2W)
  • Page 17: Option Code Of Hydro Unit

    AE090MNYDGH/EU 0 5 0 0 0 0 - 1 0 0 0 0 0 - 2 0 0 3 0 0 16.0kW AE160MNYDGH/EU 0 5 0 0 0 0 - 1 0 0 0 0 0 - 2 0 0 3 0 0 Samsung Electronics...
  • Page 18: Accessory And Option Specifications

    DVM, CAC, EHS Control System Controller Wireless Remote MR-EH00 Controller MIM-C02N S-Converter DVM, CAC, EHS Installation /Test run Solution S-NET Pro2 DVM, CAC, EHS External Room MRW-TA DVM, CAC, EHS Sensor Others MIM-H03N Wi-Fi Kit DVM, CAC, EHS Samsung Electronics...
  • Page 19: Piping

    2-6-2 Piping Product Image Model Remark Y-Joint MXJ-YA1509M 15.0 kW and below MEV-E24SA 1 Indoor MEV-E32SA MXD-E24K132A MXD-E24K200A 2 Indoor EEV KIT MXD-E32K200A MXD-E24K232A MXD-E24K300A 3 Indoor MXD-E32K224A MXD-E32K300A Samsung Electronics...
  • Page 20: Indoor

    Cassette, Wall-mount, Ceiling, Duct, Console sensor MDP-M075SGU1D MSP Duct (9.0 / 11.2 kW) MDP-M075SGU3D MSP Duct (5.6 / 7.1 kW) MDP-E075SEE3D Silm Duct (2.0~14.0 kW) Drain Pump MDP-G075SP Duct S (External, All Capacities) MDP-G075SQ Duct S (Internal, 3.5 kW~14kW) Samsung Electronics...
  • Page 21: Disassembly And Reassembly

    Gas leak detector Gas leak test Need exclusive one. (Ones used for R-134a is compatible) Must use the flare nut equipped with the product. Flare nut Refrigerant leakage may occur when the conventional flare nut for R-22 is used. Samsung Electronics...
  • Page 22: Disassembly And Reassembly

    3-2 Disassembly and Reassembly Hand Tool sets Item Remark +Screw Driver Adjustable wrench –Screw Driver Nipper Electric Motion Driver L-Wrench Torque Lench Latchet Lench Samsung Electronics...
  • Page 23: Hydro Unit

    1) Remove 3 screws from it. & (Use + Screw Driver) Manometer 2) Remove pressure sensor by adjustable wrench. (Use adjustable wrench-230kgf·cm) 3) Pull the manometer out. 4) Push the 2 hooks of cover. 5) Pull the bottom of remocon body up. Samsung Electronics...
  • Page 24 Disassembly and Reassembly Parts Procedure Remark 5) Remove the connector from the PCB board. 6) Remove the upper case of the controller. 7) Remove 5 screws. Set a side the drain pan and hydro unit. Samsung Electronics...
  • Page 25 1) Remove 4 screws. (Use + Screw Driver) 2) Remove the cabi-control top. 3) Remove the flow switch and connector. 4) Remove a pipe from the backup Heater. (Use adjustable wrench-380kgf·cm) Use the Torque Wrench when you assemble it. Samsung Electronics...
  • Page 26 Disassembly and Reassembly Parts Procedure Remark 5) After removing insulation material, remove the Thermostat. 6) Remove 2 screws. (Use + Screw Driver) 7) Remove 2 screws. (Use + Screw Driver) 8) Pull the water pump & pipes up, out. Samsung Electronics...
  • Page 27 Use the Torque Wrench when you assemble it. 2) Remove 2 screws. (Use + Screw Driver) 3) After removing the nut. Pull the bracket out. 4) Pull the expansion vessel up, out. Plate Heat 1) Remove 4 insulations. Exchanger Samsung Electronics...
  • Page 28 PCB of the Control box. 4) Remove the pipe from the Backup Heater. (Use adjustable wrench-380kgf·cm) Use the Torque Wrench when you assemble it. 5) Remove 6 screws. (Use + Screw Driver) 6) Pull the PHE out of the unit. Samsung Electronics...
  • Page 29 Disassembly and Reassembly Parts Procedure Remark Control Box 1) Remoce Thermostats and connectors 3 Phase (AE✳✳✳MNYDGH) 1 Phase (AE✳✳✳MNYDEH) 2) Remove 3 screws. (Use + Screw Driver) 3) Pull the cabi-control bottom out by pushing as indicated diretion. Samsung Electronics...
  • Page 30 Disassembly and Reassembly Parts Procedure Remark Backup Heater 1) Remove the Drain Hose. 2) After removing 4 screws, set a side the backup heater and the unit. (Use + Screw Driver) Samsung Electronics...
  • Page 31: Outdoor Unit

    1) Unscrew and remove the one screw CONTROL on the ASSY COVER CONTROL. (Use '+' type screw driver) GUARD COND 1) Pull the sensor from Guard Cond. 2) Unscrew and remove the four screws on the GUARD COND. (Use ‘+’type screw driver) Samsung Electronics...
  • Page 32 CABI BACK RH. (Use '+' type screw driver) 2) Pull the sensor from the CABI SIDE RH. CABI FRONT 1) Unscrew and remove the 9 screws on the CABI FRONT. (Use '+' type screw driver) Samsung Electronics...
  • Page 33 2) Unscrew and remove the four motor screws. (Use '+' type screw driver) 3) Disconnect the motor wire from the Ass'y Control Out. BRACKET 1) Unscrew and remove the two screws on the BRACKET MOTOR. (Use '+' type screw driver) Samsung Electronics...
  • Page 34 Disassembly and Reassembly Parts Procedure Remark CONTROL OUT 1) Disconnect the six connectors from the ASSY CONTROL OUT. 2) Unscrew and remove the two screws on the CONTROL OUT. (Use '+' type screw driver) 3) Separate the ASSY CONTROL OUT Samsung Electronics...
  • Page 35 Parts Procedure Remark ASSY-VALVE 4WAY 1) Purge the coolant first. 2) Separate the pipe from the Entrance/Exit using a welder. When removing the compressor,heat exchanger and pipe, purge the completely and remove the pipe with a welding flame. Samsung Electronics...
  • Page 36 Disassembly and Reassembly Parts Procedure Remark COMPRESSOR 1) Separate the COMPRESSOR FELT SOUND. 2) Unscrew and remove the nut on the COVER TERMINAL. (Use adjustable wrench) 3) Separate the compressor wire. 4) Separate the COMPRESSOR FELT SOUND. Samsung Electronics...
  • Page 37 Disassembly and Reassembly Parts Procedure Remark 5) As shown in the picture, unscrew and bottom. (Use Adjustable Wrench) ASSY COND OUT 1) Unscrew and remove the four screws as shown in the picture. (Use '+' type screw driver) Samsung Electronics...
  • Page 38 1) Unscrew and remove the nine screws on each side of the CABI TOP. (Use '+' type screw driver) CABI INSTALL 1) Unscrew and remove the screw FRONT on the CABI INSTALL FRONT. (Use '+' type screw driver) Samsung Electronics...
  • Page 39 Disassembly and Reassembly Parts Procedure Remark GUARD COND 1) Pull the sensor from Guard Cond. 2) Unscrew and remove the four screws on the GUARD COND. (Use '+' type screw driver) Samsung Electronics...
  • Page 40 Disassembly and Reassembly Parts Procedure Remark CABI BACK RH 1) Pull the sensor from the CABI BACK RH. 2) Unscrew and remove the nine screws on each side the CABI BACK RH. (Use '+' type screw driver) Samsung Electronics...
  • Page 41 Disassembly and Reassembly Parts Procedure Remark CABI INSTALL BACK 1) Unscrew and remove the 8 screws on the CABI FRONT LF. (Use '+' type screw driver) Samsung Electronics...
  • Page 42 Disassembly and Reassembly Parts Procedure Remark Samsung Electronics...
  • Page 43 Disassembly and Reassembly Parts Procedure Remark 1) Turn the two nuts as shown in the picture and remove them. (Use adjustable wrench) Samsung Electronics...
  • Page 44 Disassembly and Reassembly Parts Procedure Remark MOTOR 1) Remove the fan. 2) Unscrew and remove the eight motor screws. (Use '+' type screw driver) 3) Disconnect the motor wire from the Ass'y Control Out. Samsung Electronics...
  • Page 45 Disassembly and Reassembly Parts Procedure Remark BRACKET MOTOR 1) Unscrew and remove the two screws on the BRACKET MOTOR. (Use ‘+’type screw driver) Samsung Electronics...
  • Page 46 Disassembly and Reassembly Parts Procedure Remark CONTROL OUT 1) Disconnect the six connectors form the ASSY Control OUT 2) Unscrew and remove the three screws on the CONTROL OUT. (Use '+' type screw driver) 3) Separate the ASSY CONTROL OUT. Samsung Electronics...
  • Page 47 SERVICE VALVE. (Use '+' type screw driver) 3) Separate the pipe from the Entrance/Exit using a welder. When removing the compressor, heat exchanger and pipe, purge the completely and remove the pipe with a welding flame. Samsung Electronics...
  • Page 48 Remark COMPRESSOR 1) Unscrew and remove the nut on the COVER TERMINAL. (Use adjustable wrench) 2) Separate the compressor wire. 3) Separate the COMPRESSOR FELT SOUND. 4) As shown in the picture, unscrew and bottom. (Use Adjustable Wrench) Samsung Electronics...
  • Page 49 Disassembly and Reassembly Parts Procedure Remark ASSY COND OUT 1) Unscrew remove the two screws on each side of the ASSY COND OUT. (Use '+' type screw driver) Samsung Electronics...
  • Page 50 1) Unscrew and remove the nine screws on each side of the CABI TOP. (Use '+' type screw driver) CABI INSTALL 1) Unscrew and remove the screw FRONT on the CABI INSTALL FRONT. (Use '+' type screw driver) Samsung Electronics...
  • Page 51 Disassembly and Reassembly Parts Procedure Remark GUARD COND 1) Pull the sensor from Guard Cond. 2) Unscrew and remove the four screws on the GUARD COND. (Use '+' type screw driver) Samsung Electronics...
  • Page 52 Disassembly and Reassembly Parts Procedure Remark CABI BACK RH 1) Pull the sensor from the CABI BACK RH. 2) Unscrew and remove the nine screws on each side the CABI BACK RH. (Use '+' type screw driver) Samsung Electronics...
  • Page 53 Disassembly and Reassembly Parts Procedure Remark CABI INSTALL BACK 1) Unscrew and remove the 8 screws on the CABI FRONT LF. (Use '+' type screw driver) Samsung Electronics...
  • Page 54 Disassembly and Reassembly Parts Procedure Remark Samsung Electronics...
  • Page 55 Disassembly and Reassembly Parts Procedure Remark 1) Turn the two nuts as shown in the picture and remove them. (Use adjustable wrench) Samsung Electronics...
  • Page 56 Disassembly and Reassembly Parts Procedure Remark MOTOR 1) Remove the fan. 2) Unscrew and remove the eight motor screws. (Use '+' type screw driver) 3) Disconnect the motor wire from the Ass'y Control Out. Samsung Electronics...
  • Page 57 Disassembly and Reassembly Parts Procedure Remark BRACKET MOTOR 1) Unscrew and remove the two screws on the BRACKET MOTOR. (Use ‘+’type screw driver) Samsung Electronics...
  • Page 58 Disassembly and Reassembly Parts Procedure Remark CONTROL OUT 1) Disconnect the six connectors form the ASSY Control OUT 2) Unscrew and remove the three screws on the CONTROL OUT. (Use '+' type screw driver) 3) Separate the ASSY CONTROL OUT. Samsung Electronics...
  • Page 59 SERVICE VALVE. (Use '+' type screw driver) 3) Separate the pipe from the Entrance/Exit using a welder. When removing the compressor, heat exchanger and pipe, purge the completely and remove the pipe with a welding flame. Samsung Electronics...
  • Page 60 Remark COMPRESSOR 1) Unscrew and remove the nut on the COVER TERMINAL. (Use adjustable wrench) 2) Separate the compressor wire. 3) Separate the COMPRESSOR FELT SOUND. 4) As shown in the picture, unscrew and bottom. (Use Adjustable Wrench) Samsung Electronics...
  • Page 61 Disassembly and Reassembly Parts Procedure Remark ASSY COND OUT 1) Unscrew remove the two screws on each side of the ASSY COND OUT. (Use '+' type screw driver) Samsung Electronics...
  • Page 62: Troubleshooting

    4. Troubleshooting 4-1 Error Display <AE090/120/160MXTP✳✳> < AE044/066MXTP✳✳> Samsung Electronics...
  • Page 63: Service Operation

    Inverter pump frequency of 100s digit 10s digit 1s digit hydro unit Inlet water temperature 10s digit 1s digit First decimal Outlet water temperature 10s digit 1s digit First decimal Number of connected indoor 10s digit 1s digit units Samsung Electronics...
  • Page 64 Defrost temperature constant (α) = MID Defrost temperature constant (α) = MID Defrost temperature Main correction Defrost temperature constant (α) = LOW1 Defrost temperature constant (α) = LOW2 Automatic address setting Channel address Main Automatic address setting 00 to 15 0 to 15 Samsung Electronics...
  • Page 65: Tdm Plus Eeprom Code Tabel

    4-2-2 TDM PLUS EEPROM Code Tabel Model Name Inverter PBA EEPROM CODE AE044MXTPEH DB92-03544C DB82-03865A AE066MXTPEH DB92-03544C DB82-03866A AE090MXTPEH DB92-03686C DB82-03867A AE090MXTPGH DB92-03688A DB82-03868A AE120MXTPEH DB92-03687A DB82-03869A AE120MXTPGH DB92-03688A DB82-03870A AE160MXTPEH DB92-03687A DB82-03871A AE160MXTPGH DB92-03688A DB82-03872A Samsung Electronics...
  • Page 66: Wired Remote Controller Error Code

    E-458 Outdoor fan 1 error E-461 Error due to operation failure of inverter compressor 1 E-462 Compressor stop due to full current control or error due to low current on CT2 E-463 OLP over heat and comp stop Samsung Electronics...
  • Page 67 Water outlet (PHE) temp sensor error (Short/Open) E-904 Water tank temp sensor error (Short/Open) E-906 Refrigerant gas inlet temp sensor error (Short/Open) E-911 Flow switch open error E-912 Flow switch close error E-914 Thermostat wrong connection error E-916 Mixing valve temp sensor error (Short/Open) Samsung Electronics...
  • Page 68: Troubleshooting By Symptoms

    Check the communication cable in the outdoor unit PCB and replace the PCB Reconnect the cable connecting the outdoor unit to the indoor unit and restart the unit. If the communication still doesn’t work, replace the indoor unit PCB. Samsung Electronics...
  • Page 69: Hydro Unit

    Are there any problems such as short or dewetting between Replace PCB EEPROM PIN? EEPROM SUB PBA If you restart after reentering model options and power reset, does the Normal operation error occur again? Replace PCB Samsung Electronics...
  • Page 70: Error Due To Abnormal Data Of Wired Remote Controller Thermistor Value

    Temperature Resistance from the PBA Measure its resistance (°C) (KΩ) value B/W two terminal. Is the resistance value Deviated from the temp. table, 12.1 significantly? 18.0 27.3 43.0 Re-start after replacing PBA. The thermistor needs to be replaced. Samsung Electronics...
  • Page 71: Water Pump & Flow Switch Off

    Re-start after replacing PBA. Is it proper? E911 Change water flow rate to proper level Water pump ON ( Flow S/W off ) Water flow > 12LPM (AE160MNYD Water pump ON ( Flow S/W off ) : NOT enough water flow Samsung Electronics...
  • Page 72: Water Pump & Flow Switch On

    Is it short? Measure status of PBA is OPEN or SHORT? Flow S/W needs to be replaced. Is it short? Does the water flow? Does any extra PBA needs to be replaced water pump installed? Check the extra pump Samsung Electronics...
  • Page 73: Hydro Unit Temperature Sensor(Open/Short)

    137.8 (replace) 165.7 Restart the system after replacing the PCB 242.5 295.4 362.4 <103 Type> Current Resistance temperature (kΩ) (°C) 3.03 3.59 4.17 4.93 5.84 6.95 Error Mode Sensor Type 8.32 E121,E122,E123, E901,E902,E903, 12.08 E906,E916 14.68 E904 17.94 Samsung Electronics...
  • Page 74: Communication Error After Finishing Tracking(Hydro Unit)

    PCB and replace the PCB Reconnect the cable connecting the outdoor unit to the Hydro unit unit and restart the unit. If the communication still doesn’t work, replace the Hydro unit unit PCB. Samsung Electronics...
  • Page 75: Items To Check Before Diagnostics

    10s digit 1s digit °C long-1 Main Micom version Year(Dec) Month(Hex) Day(two digit) Day(One digit) long-1 and 1 Inverter Micom version Year(Hex) Month(Hex) Day(two digit) Day(One digit) long-1 and 2 EEPROM version Year(Hex) Month(Hex) Day(two digit) Day(One digit) Samsung Electronics...
  • Page 76: Troubleshooting For Outdoor Unit

    MAIN Over current trip / PFC over current error Check OLP sensor E463 MAIN/INVERTER IPM(IGBT Module) Over Current(O.C) E464 MAIN/INVERTER Comp. Over load error E465 Check AC Power or MAIN/INVERTER DC-Link voltage under/over error E466 DC_Link voltage Blink Samsung Electronics...
  • Page 77 Water outlet Check Water MAIN E903 temperature sensor error outlet sensor Refriqerant gas inlet Check Gas MAIN E906 temperature sensor error inlet sensor Mixing Valve Outlet Check Mixing Valve MAIN E916 temperature sensor error Outlet sensor Blink Samsung Electronics...
  • Page 78: Troubleshooting By Symptoms

    If the communication still doesn’t work, replace the comm. kit PCB and outdoor unit PCB in order of mention. Good +0.7V -0.7V cf.) If there is no oscillo scope, it can be replaced multimeter instead of osillo scope. Samsung Electronics...
  • Page 79: Time Out (1Min.) Of Communication Error Between Main Pba And Inv. Pba (E203)

    Does the communication error occur? Normal operation Is the communication/power cable connected properly between Connect the connector right position MAIN PBA and INVERTER PBA? Exchange MAIN PBA/INVERTER PBA in order of mention <CN305 in MAIN PBA > <CN31 in INVERTER PBA> Samsung Electronics...
  • Page 80 (*) ex) 10.17k ex) 205.4k Power on <outdoor, condenser temp. sensor> <discharge, OLP temp. sensor> (*)Resistance value for temperature sensor Is the wire of sensor broken or is there any poor contact? the temperature sensor Samsung Electronics...
  • Page 81: Fan Error (E458, E475)

    1-6V during the operation? Is the Fan in rotation during Exchange the FAN motor not in rotation TEST operation in cooling mode # TEST operation # press K1 or K2 button on the MAIN PCB after power on. Cont. Samsung Electronics...
  • Page 82 Is the Pin voltage #6 - #3 of CN90 and 91 Exchange INVERTER PCB changed high(4-5V) and low(0-1V) in case of making manual rotation slowly? Is the Pin voltage #7 - #3 of CN90 and Exchange the FAN motor 91 low(0-1V) in normal rotation? Exchange INVERTER PCB Samsung Electronics...
  • Page 83: Compressor Error (E461, E467)

    Exchange the compressor smaller than 2 (*) U↔V, V↔W, W↔U Is the value of resistance mega between compressor Exchange the compressor and outdoor unit body? Is the wire of compressor Check the wire of compressor connected correctly? Samsung Electronics...
  • Page 84: Current Trip Error (E462, E463)

    Is the indoor unit installed well Reinstall after remove the obstacle according to installation manual? Does the compressor work normal? Exchange the compressor Are the service valves fully opened? Open the service valves Exchange INVERTER PCB Samsung Electronics...
  • Page 85: Ipm(Igbt Module) Over Current Error (E464)

    Are the service valves fully opened? Open the service valves Is the wire of compressor Check the wire of compressor connected correctly? Is the value of resistance between each phase(*) for compressor Exchange the compressor smaller than 2 (*) U↔V, V↔W, W↔U cont. Samsung Electronics...
  • Page 86 Troubleshooting cont. Is the value of resistance mega between compressor Exchange the compressor and outdoor unit body? Are the position and measured value of temperature sensor normal? reposition the sensor reposition the sensor Exchange INVERTER PCB Samsung Electronics...
  • Page 87: Dc-Link Voltage Under/Over Error (E466)

    Connect the power cable Is the reactor connected correctly? Check the connection of reactor Check whether a fuse has blown Exchange the fuse Does the error occur frequently? Exchange INVERTER PCB Check the input power (AC 230V ± 15%) Samsung Electronics...
  • Page 88: Gas Leak Error(E554)

    2 (*) U↔V, V↔W, W↔U Are the service valves fully opened? Open the service valves Is the evaporator sensor of Connect the sensor’s connector indoor unit connected correctly? Is refrigerant charged? Charge refrigerant Exchange INVERTER PCB Samsung Electronics...
  • Page 89: The Other Errors

    Capacity mismatching between indoor and EEPROM data is wrong. E556 outdoor. Exchange EEPROM or MAIN PBA Option code miss matching among the Option setting data is wrong. E557 indoors(only for DPM) (This error don't occur in EMF 150-AM) Samsung Electronics...
  • Page 90: In Case Of Heating At The Cooling Mode Or Cooling At The Heating Mode

    4-WAY valve coil error of 4-WAY valve coil. Dose the voltage of AC220V Exchange apply to the connector of 4-WAY the outdoor PCB. valve coil during the operation? Go to the next page 4-WAY valve main body error Samsung Electronics...
  • Page 91 Connect the connector. correctly? Check the resistance value Outdoor fan error of outdoor fan. Dose the voltage of DC300V apply to the connector of outdoor Check the motor wire. fan during the operation of outdoor unit? Outdoor PCB error Samsung Electronics...
  • Page 92: Outdoor Unit Is Not Powered On - Initial Diagnosis

    Are the option DIP switches the option DIP switches inside the wired remote controller co ured correctly? Is there an error Check the system depending message displayed on the wired remote on the error display controller display? Check the target temperature Samsung Electronics...
  • Page 93: Outdoor Unit Power Supply Error

    CN39(MAIN PCB),CN31(INVERTER PCB) Error 203 display ALL OFF Is the FUSE on INVERTER PCB blown? Exchange the FUSE Check each BLDC FAN motor short or not, by resistance between Exchange FAN motor pin #1 and #3 Exchange INVERTER PCB Samsung Electronics...
  • Page 94: Pcb Diagram

    5. PCB Diagram 5-1 Hydro unit 17 16 15 14 13 This Document can not be used without Samsung’s authorization. Samsung Electronics...
  • Page 95 CNS045 MIXING SENSOR SMW250-02 BLU CNS047 HEATER SMW250-02 BLK HEATER/EVA-OUT/EVA-IN/WATER- CNS043 SMW250-10 WHT OUT/WATER-IN CNS201 SUB_LED SMW200-07 WHT CNS2 FR_CONTROL AKZ350 GRN CNS301 DOWNLOAD YDW200-20 BLK CN101 EARTH YDW236-01 WHT CNP401 B/UP HEATER_N YW396-02V WHT CNP003 MC2-B YTR250 Samsung Electronics...
  • Page 96: Outdoor Unit

    5-2 Outdoor Unit MAIN PCB (AE090/120/140/160MXTPEH/EU , AE090/120/140/160MXTPGH/EU) This Document can not be used without Samsung’s authorization. Samsung Electronics...
  • Page 97 A2A VALVE YW396-03AV BLK CN702 4WAY VALVE YW396-03AV YEL CN701 HOTGAS YW396-03AV RED CN101 AC POWER YW396-03AV WHT CN806 EEPROM B7P-MQ WHT CN304 DRED DAPC-2009-6P BLK CN501 MODE SELECTOR SMW250-03 WHT CN103 EARTH YDW236-01 WHT CN303 COMM-INDOOR YW396-02V RED Samsung Electronics...
  • Page 98 PCB Diagram INVERTER PCB (AE090MXTPEH/EU) This Document can not be used without Samsung’s authorization. Local Function Description CN901 FAN1 YW396-06V WHT CN911 FAN2 YW396-06V WHT CN401 COMP U YTR250 CN402 COMP V YTR250 CN403 COMP W YTR250 REACTOR_A2 REACTOR_A2 YTR250...
  • Page 99 PCB Diagram INVERTER PCB (AE120/160MXTPEH/EU) This Document can not be used without Samsung’s authorization. Local Function Description CN901 FAN1 YW396-06V WHT CN911 FAN2 YW396-06V WHT CN401 COMP 42819-3213 BLK REACTOR_A2 REACTOR_A2 YTR250 REACTOR_A1 REACTOR_A1 YTR250 REACTOR_B2 REACTOR_B2 YTR250 REACTOR_B1 REACTOR_B1...
  • Page 100 PCB Diagram INVERTER PCB (AE090/120/160MXTPGH/EU) This Document can not be used without Samsung’s authorization. Local Function Description CN351 COMM-MAIN SMW250-06 WHT CN400 COMP 42819-3213 BLK CN101 REACTOR HLW1005-02 BLK CN102 R-IN YTR250 CN103 S-IN YTR250 CN104 T-IN YTR250 CN150 AC POWER...
  • Page 101 PCB Diagram EMI PCB (AE090/120/160MXTPEH/EU) This Document can not be used without Samsung’s authorization. Local Function Description AC POWER OT-048 EARTH EARTH YEL/GRN WIRE AC POWER BRN WIRE AC POWER SKY/BLU WIRE AC POWER OT-048 CN01 AC POWER YW396-03AV WHT...
  • Page 102 PCB Diagram EMI PCB (AE090/120/160MXTPGH/EU) This Document can not be used without Samsung’s authorization. Local Function Description EARTH EARTH YEL/GRN WIRE R-IN R-IN WHT WIRE S-IN S-IN BRN WIRE T-IN T-IN BLK WIRE N-IN N-IN SKY/BLU WIRE N-INV N-INV SKY/BLU WIRE...
  • Page 103 PCB Diagram INVERTER PCB (AE044/060MXTPEH/EU) This Document can not be used without Samsung’s authorization. Samsung Electronics...
  • Page 104 YW396-03AV BLU CN301 COMM YW396-02V RED CN205 SUB PBA SMW200-05 BLK CN251 OUT/DISCHARGE/COND/OLP SMAW200-08 WHT CN245 SUCTION SMAW250-02 WHT CN252 WATER SMAW250-04 YEL CN702 SMW250-06 BLU CN801 LOW PRESSURE SENSOR B04B-XAEK-1 BLU CN809 HIGH PRESSURE SENSOR B04B-XARK-1 RED Samsung Electronics...
  • Page 105 PCB Diagram SUB-DISPLAY PCB (AE044/060MXTPEH/EU) This Document can not be used without Samsung’s authorization. Local Function Description OPT1 MODE SELECTOR SMW250-03 WHT CN518 DC POWER SMW200-05 BLK CN502 MAIN-SUB SIGNAL SMW200-10 BLK CN511 DC12V YW396-02V BLU CN501 MAIN-SUB SIGNAL SMW200-10 BLU...
  • Page 106: Wiring Diagram

    6. Wiring Diagram 6-1 Hydro unit 6-1-1 1Phase Model This Document can not be used without Samsung’s authorization. Samsung Electronics...
  • Page 107: 3Phase Model

    6-1-2 3Phase Model This Document can not be used without Samsung’s authorization. Samsung Electronics...
  • Page 108: Outdoor Unit

    6-2 Outdoor Unit 1Phase (AE044/066MXTPEH) This Document can not be used without Samsung’s authorization. Samsung Electronics...
  • Page 109 Wiring Diagram 1Phase (AE090/120/160MXTPEH) This Document can not be used without Samsung’s authorization. Samsung Electronics...
  • Page 110 Wiring Diagram 3Phase (AE090/120/160MXTPGH) This Document can not be used without Samsung’s authorization. Samsung Electronics...
  • Page 111: Piping Diagram

    Wiring Diagram 7. Piping Diagram 7-1 Piping Diagram AE090MNYP** Water Pump Cooling mode Heating mode (Water flow) Samsung Electronics...
  • Page 112 Wiring Diagram 7-1 Piping Diagram (cont.) AE160MNYP** Water Pump Cooling mode Heating mode (Water flow) Samsung Electronics...
  • Page 113 Wiring Diagram 7-1 Piping Diagram (cont.) AE040/066MXTP** Heat exchanger Cooling mode Heating mode (Water flow) Samsung Electronics...
  • Page 114 Wiring Diagram 7-1 Piping Diagram (cont.) AE090MXTP** Heat exchanger Cooling mode Heating mode (Water flow) Samsung Electronics...
  • Page 115 Wiring Diagram 7-1 Piping Diagram (cont.) AE120/160MXTP** Heat exchanger Cooling mode Heating mode (Water flow) Samsung Electronics...
  • Page 116: Reference Sheet

    WATT(*100) WATT(*100) Series version WATT(*100) WATT(*100) WATT(*100) WATT(*100) STANDRAD (/STANDARD TANK) WATT(*100) MULTI (Premium) WATT(*100) Power WATT(*100) E(220~240V, 50Hz, 1Ø) G(380~415V, 50Hz, 3Ф) Mode Year HEAT PUMP R410a 2017 Outdoor / Inodoor Indoor unit (NASA) Outdoor unit (NASA) Samsung Electronics...
  • Page 117 China china.samsungportal.com © Samsung Electronics Co., Ltd. Feb. 2017. This Service Manual is a property of Samsung Electronics Co., Ltd. Any unauthorized use of Manual can be punished under applicable Printed in China. International and/or domestic law. Code No. AC-07002A_0...