Article number
Ambient conditions
Ambient temperature during operation
•
•
Ambient temperature during stor-
age/transportation
•
•
•
•
Air pressure acc. to IEC 60068-2-13
•
•
•
•
Altitude during operation relating to sea level
•
Relative humidity
•
•
Vibrations
•
•
Shock testing
•
•
Dimensions
Width
Height
Depth
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
min.
max.
Storage, min.
Storage, max.
Transportation, min.
Transportation, max.
Operation, min.
Operation, max.
Storage, min.
Storage, max.
Installation altitude above sea level, max.
Operation at 25 ℃, max.
Operation at 50 ℃, max.
Vibration resistance during operation acc.
to IEC 60068-2-6
Vibration resistance during storage acc. to
IEC 60068-2-6
Shock resistance during operation acc. to
IEC 60068-2-27
Shock resistance during storage acc. to
IEC 60068-2-29
Technical specifications
13.4 Technical specifications for I/O module
6BK1900-0CA00-0AA0
0 °C
55 °C
-25 °C
70 °C
-25 °C
70 °C
860 hPa
1 080 hPa
660 hPa
1 080 hPa
2 000 m
95 %
50 %; 95 % at 25 °C, decreasing linearly to 50 %
at 50 °C
10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1 g
5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1 g
15 g / 11 ms / 3 shocks/axis
25 g / 6 ms / 1 000 shocks/axis
27 mm
141 mm
110 mm
187