Section 7
Logical node data model
7.9
7.9.1
Table 182:
SSCBR Logical node data
DO name
DO type
Mod
a_dINC
Beh
a_dINS
InaTmdCnt
v1_dINS
RmnLifPhA
v1_dINS
RmnLifPhB
v1_dINS
RmnLifPhC
v1_dINS
Table continues on next page
264

Logical nodes for sensors and monitoring

Circuit breaker monitoring SCBR

LN type
LN prefix LN class Function block name
SSCBR (revision 1) S
DA name
FC
Oper.ctlVal
CO
Oper.origin.orCat
CO
Oper.origin.orIdent
CO
Oper.ctlNum
CO
Oper.T
CO
Oper.Test
CO
Oper.Check
CO
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
stVal
ST
SCBR
SSCBR
T
Signal
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Beh
-
Beh
-
Beh
-
INA_DAYS
-
INA_DAYS
-
INA_DAYS
-
CB_LIFE_A
-
CB_LIFE_A
-
CB_LIFE_A
-
CB_LIFE_B
-
CB_LIFE_B
-
CB_LIFE_B
-
CB_LIFE_C
1MRS756793 E
Mon/C
Description
md
Cmd
Mode parameter for 61850
Cmd
Mode parameter for 61850
Cmd
Mode parameter for 61850
Cmd
Mode parameter for 61850
Cmd
Mode parameter for 61850
Cmd
Mode parameter for 61850
Cmd
Mode parameter for 61850
Mon
Mode status parameter for 61850
Mon
Quality: Mode status parameter for
61850
Mon
Timestamp: Mode status
parameter for 61850
Mon
Behaviour parameter for 61850
Mon
Quality: Behaviour parameter for
61850
Mon
Timestamp: Behaviour parameter
for 61850
Mon
The number of days CB has been
inactive
Mon
Quality: The number of days CB
has been inactive
Mon
Timestamp: The number of days
CB has been inactive
Mon
CB Remaining life phase A
Mon
Quality: CB Remaining life phase
A
Mon
Timestamp: CB Remaining life
phase A
Mon
CB Remaining life phase B
Mon
Quality: CB Remaining life phase
B
Mon
Timestamp: CB Remaining life
phase B
Mon
CB Remaining life phase C