Siemens SINAMICS S120 Equipment Manual page 60

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
3.2 Active Interface Modules
,
Figure 3-11
The dimensions of the typical cabinet (Rittal TS8) are (width x height x depth) 600 mm x
2200 mm x 600 mm
There must be a minimum clearance of 970 mm between the lower edge of the transport
plate (
The insulating mat between the filter reactor and the filter module is made of "AF/Armaflex
AF-19MM/EA" and has the following properties:
● Thickness: 19 mm
● Thermal conductivity: ≤ 0.033 W/(m x K)
● Upper application temperature: 110 °C
● UL certification
● Self-adhesive
The entries for the cables and hoses should be made so that there is no heat loss (e.g.
cross-shaped cuts).
The lateral insulating mats are made of "HT/Armaflex HT-10-99/E" and have the following
properties:
● Thickness: 10 mm
● Thermal conductivity: ≤ 0.042 W/(m x K)
● Upper application temperature: 150 °C
● UL certification
● Not self-adhesive (are held by the lugs of the lateral holding plate)
Additional insulating mats made of the same material should be attached to the front and
rear of the control cabinet.
60
Connections (U1, V1, W1) at the filter module to establish the connection to the line side of
the filter reactor (U1, V1, W1)
Partition plate (not included in the scope of supply) to stabilize the thermally insulating mat
between the filter reactor and the filter module (
Hose between the return and filter reactor (P1)
Hose between the intake and filter module (P7)
PE connection between the PE rail and filter module
Support plate (not included in the scope of supply) for the filter reactor
PE rail (not included in the scope of supply)
Intake (not included in the scope of supply)
Return (not included in the scope of supply)
Holding plate for lateral insulating mats, attached to all 4 sides of the cabinet (not included in
the scope of supply)
Lateral insulating mats, attached to all 4 sides of the cabinet (not included in the scope of
supply)
Insulating mat between the filter reactor and filter module (not included in the scope of sup-
ply)
Mounting bracket (not included in the scope of supply) to mount the partition plate between
the filter reactor and the filter module (
Mounting space for DC busbars, 200 mm high
Typical control cabinet design, Rittal TS8, cabinet width 600 mm
) and the lower edge of the filter module.
)
)
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0

Advertisement

Table of Contents
loading

Table of Contents