5.1.7

Sensor insulation

Fig. 14: Insulation of the meter tube
1 Insulation
The piping can be insulated up to a thickness of 100 mm
(4 inch).
5.1.8

Use of trace heating

Trace heating may be used under the following conditions:
— If it is installed directly on or around the piping
— If, in the case of existing pipeline insulation, it is installed
inside the insulation (the maximum thickness of
100 mm [4 inch] must not be exceeded)
— If the maximum temperature the trace heating is able to
produce is less than or equal to the maximum medium
temperature.
NOTICE
The installation requirements set out in EN 60079-14 must be
observed.
Please note that the use of trace heaters will not impair EMC
protection or generate additional vibrations.
5.2
5.2.1
Ambient temperature
In accordance with IEC 60068-2-78
Explosion
1
protection
No explosion
protection
Ex ia, Ex nA
G11762
Ex d ia, XP-IS
IS, NI
1) The temperature xx °C (xx °F) depends on the temperature class T
Relative humidity
Version
Standard
Measuring medium temperature range
Version
Standard
High-temperature
design (option)
[°C]
85
80
70
60
50
40
30
20
10
–10
-20/-40
Fig. 15: Measuring medium temperature T
1 Permissible temperature range standard version 2 Permissible
temperature range high temperature version (option)
VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 | CI/FSV/FSS/430/450-EN Rev. G 23

Environmental conditions

FSV430, FSV450

Ambient temperature range T
Standard
-20 ... 85 °C
(-4 ... 185 °F)
-20 °C < Ta < xx°C
(-4°F < Ta < xx °F)
-20 ... 75 °C
(-4 ... 167 °F)
-20 °C < Ta < xx°C
(-4°F < Ta < xx °F)
Relative humidity
Maximum 85 %, annual average ≤ 65 %
T
medium
-55 ... 280 °C (-67 ... 536 °F)
-55 ... 400 °C (-67 ... 752 °F)
1
0
-55
0
50
100
150 160 200
-67
32
122
212
302 320 392
T
medium
ambient temperature T
amb.
amb.
Advanced mode
-40 ... 85 °C
(-40 ... 185 °F)
1)
-40 °C < Ta < xx °C
1)
1)
1)
(-40°F < Ta < xx °F)
-40 ... 75 °C
(-40 ... 167 °F)
1)
1)
-40 °C < Ta < xx °C
1)
(-40°F < Ta < xx °F)
1)
class
[°F]
185
176
158
140
2
122
104
86
68
50
32
14
-4/-40
250
280
400 [°C]
482
536
752 [°F]
G11788-01
dependent on the
medium