Download Print this page

Specifications; Operation - Honeywell M7410E Product Data

Small modulating linear valve actuator

Advertisement

M7410E SMALL MODULATING LINEAR VALVE ACTUATOR

SPECIFICATIONS

Motor
Input voltage:
24 Vac ±15%; 50/60 Hz
Power consumption: 1.4 VA
Input signal:
modulating 0...10 V, 2...10 V
(adjustable); <0.1 mA

Operation:

direct/reverse (adjustable)
Stroke:
6.5 mm
Running time:
150 s at 50 Hz
120 s at 60 Hz
Stem force:
depending on type (see table)
180 N (for valves DN 15..20)
300 N (for valves DN 25..40 and
V5825B)
Protection standard: IP 42 in accordance with EN 60529
Insulation class:
III in accordance with EN 60730
Connection cable:
1.5 m
Ambient operating
0...55 °C
temperature limits:
Weight:
0.4 kg
Suitable valves:
see table
Manual operation:
see table
VERSIONS
Standard
With manual
operation
With manual
operation and
auxiliary switches
Special versions
EN0B-0097GE51 R1004
Stem
Manual operation
force
Provided by the valve
180 N
adjustment cap
300 N
Integrated
180 N
"
300 N
Integrated
180 N
"
300 N
Special cable length
length = 3 m / 5 m / 10 m
Auxiliary Switches
Ratings:
5...24 V max. 100 mA
24...230 Vac, max. 3(1) A
Switch position
Switch S1 (fix)
(factory supplied):
Switch S2 (adjust.)
OPERATION
The movement of the electric actuator is produced by a screw
spindle which is driven in both directions by a synchronous
motor through a set of gears. A magnetic clutch limits the
torque of the gear assembly and the driving force of the
actuator. The actuator is fixed to the valve body by means of
a coupling ring requiring no tools for mounting. The actuator
is maintenance-free and supplied completely with a ready-to-
wire connecting cable.
A microprocessor-based high performance positioner
guarantees accurate control. The close-off position is self-
adjusting by means of an automatic synchronization function.
Synchronization is performed when the applied control signal
is 0 V or 10 V. The actuator then drives every minute for 5
seconds into the end position in order to ensure close-off
even after manual operation.
Aux.
Aux.
switch S1
switch S2
x
x
x
x
2
17.8 ± 0.2 mm
11.7 ± 0.2 mm
Housing
OS number
type
B
M7410E1002
B
M7410E1028
C
M7410E2026
C
M7410E2034
C
M7410E4022
C
M7410E4030
upon request