Installation Instructions for the
PX2 Series Heavy Duty Transducers
GENERAL INFORMATION
Honeywell's PX2 Series Heavy Duty Pressure Transducer is
a portfolio of highly configurable pressure sensors that use
piezoresistive sensing technology with ASIC (Application Specific
Integrated Circuit) signal conditioning in a stainless steel housing.
The PX2 Series is fully calibrated and compensated for offset,
sensitivity, temperature effects and non-linearity using the on-
board ASIC.
OVERPRESSURE
CAUTION
PRODUCT DAMAGE
• Do not exceed the overpressure.
Failure to comply with these instructions may result in
product damage.
If the overpressure rating is exceeded, the life of the PX2 Series
may be reduced and electrical failure may occur. Both static
and dynamic overpressure must be considered, particularly in
hydraulic system applications. Hydraulic pressure fluctuations
can have very high and very fast peak pressures, as in a water
hammer effect.
An oscilloscope is recommended for determining if high-pressure
transients exist in a system. If system pressure pulses are
expected, choose a transducer with a pressure rating high enough
to allow continuous operation at the highest expected pressure
spikes.
A pressure 'snubber' may be used to reduce the peak pressure
applied to the transducer.
MEDIA COMPATIBILTY
CAUTION
PRODUCT DAMAGE
• Use non-abrasive, chemically compatible media to prevent
damage to diaphragm or port materials.
Failure to comply with these instructions may result in
product damage.
The PX2 Series fluid path is an assembly of 304 stainless steel,
epoxy, alumina, glass, and silicon.
Table 1. Compatible Media
Refrigerants
R410A
R134A
R123ZE
mixture of R245Fa and transdichloroethylene
INSTALLATION
Sensing and Control
CAUTION
PRODUCT DAMAGE
• Ensure torque specifications are determined for the specific
application. Values provided are for reference only. NPT ports
are not specified with torque values. Correct installation
is based on the number of Turns From Finger Tight (TFFT).
(Mating materials and thread sealants can result in
significantly different torque values from one application to
the next.)
• When using NPT ports in stainless steel manifolds, use
a thread sealant with anti-seize properties to prevent thread
galling. Ensure the sealant is rated for the application.
• Use appropriate tools (such as an open ended wrench or
deep well socket) to install transducers.
• Always hand-start transducers into the hole to prevent cross
threading and damage.
• Do not subject the transducer to high temperatures from
soldering, brazing, or welding of the system plumbing
Failure to comply with these instructions may result in
product damage.
Ratiometric voltage devices require either a regulated 3.3 Vdc (AA
and AB) or a regulated 5.0 Vdc supply (AC and AD), (see Table 2).
All other versions can use an unregulated supply within the ranges
noted under the excitation specifications. Ensure the power supply
is off while wiring.
ELECTROMAGNETIC ENERGY/NOISE
CAUTION
PRODUCT DAMAGE/ERRATIC OPERATION
• Do not use in areas where electromagnetic energy may affect
transducer operation.
Failure to comply with these instructions may result in
product damage.
The PX2 Series has been rated for high immunity to electrical
noise; however, care should be taken when used around high
voltage sources that emit high levels of radiated electromagnetic
energy like variable frequency motor drives, solenoids, radio
transmitters and engine ignition systems. The use of shielded
cable and grounding of pressure port is also recommended.
FUNCTIONAL TEST
1. Connect the transducer to a dc voltage supply (off). The supply
voltage should be set within the range specified for the model.
2. Based on the transducer's specified output, connect the output
Other Media
lead(s) to a digital dc or mA meter.
engine oil 10W30
3. With no pressure on the transducer, turn on the power supply
brake fluid DOT3
and read the output signal on the voltmeter. The reading
hydraulic fluid
should correspond to the specification indicated for null offset.
tap water
compressed air
If not, check the connections, wire color code and the setting
of the power supply.
Issue 8
50052336

Advertisement

loading

Summary of Contents for Honeywell PX2 Series

  • Page 1 • Do not subject the transducer to high temperatures from If the overpressure rating is exceeded, the life of the PX2 Series soldering, brazing, or welding of the system plumbing may be reduced and electrical failure may occur. Both static...
  • Page 2: Wiring Instructions

    • If only two leads are used, any additional terminal cavities should be sealed per the connector manufacturer’s installation guide. • Honeywell recommends using a crimping tool for crimping wires to the connector terminals. • Contact the individual connector manufacturer for connector wiring.
  • Page 3 12. Turn On Time: Duration from power applied until first valid output. 13. Life may vary depending on the application in which transducer is used. Contact Honeywell Sales and Service for Mean Time to Failure (MTTF) data based on customer-specific usage profile.
  • Page 4 PX2 Series Heavy Duty Presssure Transducers ISSUE 8 50052336 Table 4. Pressure Ratings Operating Over- Burst Operating Over- Burst Operating Over- Burst Operating Over- Burst Pressure pressure Pressure Pressure pressure Pressure Pressure pressure Pressure Pressure pressure Pressure 1000 1700 1000 1700 10.3...
  • Page 5 PX2 Series Heavy Duty Pressure Transducers ISSUE 8 50052336 Figure 3. Electrical Connector Type Dimensions (For reference only: mm/[in].) Delphi Metri-Pack 150, Standard (UL 94 HB) Micro M12 (IEC 61076-2) (EN 175301-803C) Delphi Metri-Pack 150 (UL 94 V-0) Connector: DELPHI 12078088...
  • Page 6 PX2 Series Heavy Duty Presssure Transducers ISSUE 8 50052336 Figure 3. Electrical Connector Type Dimensions (continued) Cable Harness, 1 Meter Cable Harness, 2 Meter Deutsch Cable Harness, 3 Meter 2, 3 (DTM04-3P) Cable Harness, 5 Meter 2, 3 Connector: Deutsch DTM04-3P...
  • Page 7 PX2 Series Heavy Duty Pressure Transducers ISSUE 8 50052336 Figure 4. Pressure Port Type Dimensions (For reference only: mm/[in].) 22 Hex flat to flat [0.87] 7/16-20 UNF 1/4 in 45º Flare Female Schrader (SAE J512) 7/16-20 UNF 45º Flare Male (SAE J513) Seal: 45º...
  • Page 8: Customer Service

    Authorized Distribution Brand: Website: Welcome to visit www.ameya360.com Contact Us: Address: 401 Building No.5, JiuGe Business Center, Lane 2301, Yishan Rd Minhang District, Shanghai , China Sales: Direct +86 (21) 6401-6692 Email amall@ameya360.com 800077892 Skype ameyasales1 ameyasales2 Customer Service: Email service@ameya360.com Partnership:...