M6410A, M7410F ACTUATORS; V5862A, V5863A VALVES

INSTALLATION

When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check ratings given in instructions and on the product to
ensure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Severe Scalding Hazard.
Contact with hot liquid can lead to severe injury or
cause death.
For a pressurized valve, only open with Valve
Cartridge Replacement Tool. For complete safety,
release system pressure to the valve body before
changing cartridge.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
• Before installing the valve and actuator, use the
protective cover/manual handle to ensure the valve
stem operates freely. Impaired stem operation can
indicate a bent stem (due to rough handling). This
condition can require replacing the valve.
• When installing valves, make sure the flow direction
is correct by checking the arrow on the valve body.
• Mount the valve only with the stem pointing upward.
• Leave the protective cover in place until ready to
attach the actuator.
Location
Select a location where the valve and actuator are accessible.
Mounting
Valve
The valve body should be completely installed in the pipe line
before the actuator is installed.
1. Verify pipe size and flow direction for the valve being
used.
2. Position the valve so that the actuator can be easily
installed.
3. Install the valve using the applicable tools and supplies.
Follow standard practices.
Actuator
No tools are required to install the actuators on valves
because they are threaded onto the valve by hand.
63-2612—05
CAUTION
Careless Installation Hazard.
Forcibly tightening the mounting connection can
damage the valve and actuator.
Never tighten the connection with a wrench.
To mount the actuator, refer to Fig. 3 through 5. Fig. 4 shows
the M6410A, M7410F valve position indicator:
1. Remove the protective cover from the valve (Fig. 3).
2. Make sure the actuator is in the (factory-supplied)
OPEN position.
3. Screw the actuator connector onto the body of the valve
(Fig. 5).
Wiring
Connect the M6410A Actuator to the controller using the
wiring diagram for the controller. See Fig. 6 for typical hookup
to T6984F. For hookup with an Excel 10
Use the M7410F with Excel
T7984, and W7751 controllers. Power the M7410F from the
same transformer as the controller when using Excel
Systems, or T7984 Controllers, when the common lines from
the controller and the actuator are connected together and the
hot side of the 24 Vac power connection on the transformer is
used. See Fig. 8. Electrical installation must comply with
wiring diagram shown in Fig. 9.
Fig. 3. Removing protective cover from valve.
Fig. 4. Valve position indicator (M6410A shown).
4
®