4.9. Clear Fault Record Data [RECORD RESET]

By the "RECORD RESET", all record data (such as operated elements, fault measured values) are deleted.
The records are deleted 3 seconds after the Switch-1 set this position.
If password function is enabled, please refer to clause 4.6.1. Following operation steps shows the condition
after inputting correct password.
If password function is not used, the condition directly goes to following steps.
Turn Switch-1 to "RECORD
RESET" (position 13).
After the Switch-1 setting
this position, the remaining
time until the deletion is
shown in the progress bar on
7-seg LED.
The time until deletion start is
about 3 seconds.
When you would like to
CANCEL the deletion, please
change Switch-1 to other
positions until appearing three
(3) bars.
When the progress bar is
reached to third digit, the
records clear is completed.
43 / 47
JEP0-IL9537