Configuring the BACNET-GW-3
3.2.5 Additional Properties
The following table describes the options available under Additional Properties in the navigation tree (see
Figure
3.1). After configuring the settings, click Apply in the lower right corner of the window.
Navigation Tree
Label
IP Address
Settings
NFN Settings
BACNET-GW-3 Installation and Operation Manual – P/N LS10014-000NF-E:C6 5/5/2017
Table 3.3 Additional Properties
Property
IP Address Settings
IP Address
Enter the IP address of the BACNET-GW-3.
(Default is 192.168.1.2)
Note: If a new IP address is entered, the user must enter the new IP address in
the browser address bar to log into the gateway at its new address.
Subnet Mask
Enter the subnet address of the BACNET-GW-3.
(Default is 255.255.255.0)
IP Gateway
Enter the IP address of the default gateway for the host network.
(Default is 0.0.0.0)
MAC Address
Displays the Media Access Control (MAC) address of the gateway Ethernet port
and is not configurable.
DNS Server Settings
Preferred DNS
Enter the IP address of the primary Domain Name System (DNS) server.
Server
Alternate DNS
Enter the IP address of the alternate DNS server.
Server
General Information
Connection Port Displays the type of connection port used (Serial, USB, etc.)
Connection
Describes how the gateway is connected to the NFN network.
Type
NCM Version
Displays the NCM version number.
Note: This property does not appear when there is no NFN connection.
NCM Status Bits Displays the NCM status, which can be: Piezo, UPS Failure, Network Fail Port A,
Network Fail Port B, High Speed Audio, NCM Sniffer Mode Active, Local
Connection Limit Exceeded, or None.
Note: This property does not appear if/when there is no NFN connection.
Fire Network
Always displays "Accept Time" since BACNET-GW-3 does not synchronize time
Time Policy
with the network.
Node Settings
Node
Enter the NFN node number of the BACNET-GW-3.
(Default is 240)
Panel Label
Enter the panel label.
Network Settings
• Select High for a high-noise NFN network.
Channel A
Threshold
• Select Low for a low-noise NFN network.
• Select High for a high-noise NFN network.
Channel B
Threshold
• Select Low for a low-noise NFN network.
• Select Yes for a Style 7 SLC (Signaling Line Circuit) configured NFN network.
Style 7
• Select No for a Style 4 SLC configured NFN network (default).
Value
Configuration