1-8 Field Setting / Function Setting for Outdoor air unit

Classification
Address
Indoor unit field setting
setting by
Filter
remote controller
Airflow
Change of
function 1
Change of
function 2
*1: Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Select control conditions of external output.
"Mode 00" is output when heating thermostat is ON, "Mode 01" is output in heating operation, "Mode 02" is output in heating operation and in fan operation.
*3:
Threshold temperature setting for cool / heat mode under auto operation ; Set temperature +4
*
Cool / heat mode tends to be switched as the threshold temperature range gets smaller,
and cool / heat mode becomes difficult to be switched as the threshold temperature range gets larger.
Set the proper value according to use conditions.
ITEM
Setting Mode
CODE No.
00
Indoor unit address
02
Refrigerant circuit address
11
Filter indicator Interval
13
Filter sign display
26
Static Pressure setting
- Outdoor air unit Only -
The Range of static pressure is
different from one model to other.
Model name
Range of static
pressure
AAUA48TLAV
SP mode 05 to 19
(0.2 to 0.76 in.WG)
AAUA72TLAV
SP mode 05 to 20
(0.2 to 0.80 in.WG)
AAUA96TLAV
SP mode 05 to 22
(0.2 to 0.88 in.WG)
40
Auto restart *1
43
Cool air prevention
46
External control
Error report target
47
60,61,62 Forbidden
63
Humidifier control *2
65
Threshold temperature setting
for cool / heat switch over*3
ITEM
CODE No.
00~63
00~63
00~99
00~99
00
Default
Longer
01
02
Shorter
00
Enable
Disable
01
02
Display only on central remote control
SP mode 05 [ 0.20 in.WG ( 50 Pa) ]
05
06
SP mode 06 [ 0.24 in.WG ( 60 Pa) ]
07
SP mode 07 [ 0.28 in.WG ( 70 Pa) ]
08
SP mode 08 [ 0.32 in.WG ( 80 Pa) ]
09
SP mode 09 [ 0.36 in.WG ( 90 Pa) ]
SP mode 10 [ 0.40 in.WG ( 100 Pa) ]
10
SP mode 11 [ 0.44 in.WG ( 110 Pa) ]
11
SP mode 12 [ 0.48 in.WG ( 120 Pa) ]
12
Normal static
SP mode 13 [ 0.52 in.WG ( 130 Pa) ]
13
pressure
SP mode 14 [ 0.56 in.WG ( 140 Pa) ]
14
SP mode 15 [ 0.60 in.WG ( 150 Pa) ]
15
0.74 in.WG
(185 Pa)
SP mode 16 [ 0.64 in.WG ( 160 Pa) ]
16
SP mode 17 [ 0.68 in.WG ( 170 Pa) ]
17
0.80 in.WG
SP mode 18 [ 0.72 in.WG ( 180 Pa) ]
18
(200 Pa)
SP mode 19 [ 0.76 in.WG ( 190 Pa) ]
19
SP mode 20 [ 0.80 in.WG ( 200 Pa) ]
20
0.80 in.WG
SP mode 21 [ 0.84 in.WG ( 210 Pa) ]
21
(200 Pa)
SP mode 22 [ 0.88 in.WG ( 220 Pa) ]
22
Normal SP
31
00
Enable
01
Disable
00
Super low
01
Follow the setting on the remote controller
00
Start / Stop
01
Emergency stop
02
Forced stop (Start/Stop by RC is restricted)
00
All
01
Display only for central remote control
00
01
00
mode 00
01
mode 01
02
mode 02
00
mode 0 +10
mode 1 +4
01
02
mode 2 +6
03
mode 3 +8
04
mode 4 +10
mode 5 +12
05
mode 5 +14
06
°
F (+2
-
-
01-27
Setting Function
°
F (+5
°C)
-
-
°
F (+2
°C)
-
°
F (+3
°C)
-
-
°
F (+4
°C)
-
-
°
F (+5
°C)
-
-
°
F (+6
°C)
-
-
°
F (+7
°C)
-
-
°C) to
+14
°
F (+7
°C)
-
-
Default
00