Honeywell Modutrol IV 61 Series Manual page 3

Hide thumbs Also See for Modutrol IV 61 Series:
Table of Contents

Advertisement

1/4
(7)
3
AUXILARY
END
9/16 (15)
ADAPTER
BRACKET
Fig. 1. Series 61 and 62 Modutrol IV Motor mounting dimensions in inches (mm).
Table 4. Series 61 and 62 Modutrol IV Motor Timing and Torque Ratings.
a
Nominal Timing
in sec
90° Stroke
160° Stroke
15
30
30
60
60
120
120
240
a
Timings apply to all TRADELINE models. Some OEM models are available with non-standard timing/torque.
b
Torque ratings for dual-ended shaft motors are the sum of the shaft torques (power-end torque plus auxiliary-end torque).
c
Breakaway torque is the maximum torque available to overcome occasional large loads such as a seized damper or valve.
NOTE: Torque designation corresponds to torque rating at
standard timing (nominally 60 seconds for 160° and
30 seconds for 90° except for 300 lb-in. motors that
have timings of 2 or 4 minutes).
TOP VIEW
13/16
(20)
13/16
(20)
2
4-1/16 (103)
1-1/2 (37)
4-1/16 (103)
1-1/2 (37)
POWER
END
1
Normal Running Torque
Spring Return
60 (6.8)
SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS
TOP VIEW OF BRACKET
4-7/8
(124)
4-5/8
(116)
5-1/2
(140)
JUNCTION
BOX
3/4
(19)
MOTOR
6-7/16
(164)
SPRING RETURN MODEL SHOWN
5-3/8
FOR 60 LB-IN. SPRING RETURN MODELS 8-3/4 (222).
1
(137)
FOR NON-SPRING RETUIRN MODELS 7-5/16 (185).
2-9/16
2
FOR 60 LB-IN. SPRING RETURN MODELS (SHOWN).
(66)
FOR NON-SPRING RETURN MODELS.
3
3/4
(19)
Rated Torque in lb-in. (N•m)
Non-Spring Return
75 (8.5)
35 (4.0)
120 (13.6)
150 (17.0)
300 (34.0)
150 (17.0)
IMPORTANT
Never use motor continuously at the Breakaway
Torque rating.
Feedback Potentiometer (Series 62 Models Only):
TRADELINE Models (Can be shunted for slaving a
Series 90 Motor).
3
2-5/16
(58)
11/16
(17)
POWER END
1/4 (7)
4-7/8 (124)
5-9/16 (141)
b
Breakaway Torque
Spring Return
Non-Spring Return
150 (17.0)
70 (7.9)
300 (34.0)
600 (68.0)
300 (34.0)
4-1/4
(107)
5-13/16
(148)
M18998B
c
63-2629—2