Appendix 4.3
1.
Arrange timers in series to obtain necessary time.
X102
0
T9
5
T10
11
X102
Normally open
contact T9
Normally open
contact T10
Y172
2.
Use timers and counters to obtain necessary time.
Time limit of a timer × Set value of a counter = Long-time timer (Note that the accuracy of timers is accumulated.)
X102
M56
Y173
0
X102
C7
7
Y173
T14
12
Y173
C7
18
24
X102
Coil T14
Normally open
contact T14 (M56)
C7
Y173
*
Obtain necessary time by counting the number of timeouts of the timer T14 with the counter C7.
M56 resets T14 after a timeout. With C7, the output Y173 holds its ON state when counting is up. Y173 resets T14 and stops the
subsequent time counting.
Long-time timer
2000
3000 seconds
seconds
5000 seconds
One scan
900 seconds × 4 = 3600 seconds = 1 hour
K30000
T9
3000.0 seconds
K20000
T10
2000.0 seconds
Y172
Turn on this device
after the time limit
elapses.
Project name
RA-18
Program name
MAIN
K9000
T14
Turn on this device
Y173
after the time limit
elapses.
K4
C7
M56
RST
C7
END
APPENDICES
Appendix 4 Program Examples
A
App. - 9