Siemens Desigo RXC20.1 Manual page 12

Room controllers
Table of Contents

Advertisement

Connection terminals
RXC22
Note!
STOP
Tool socket
12/16
Siemens
Building Technologies
1
2
3
4
5
6
7
8
T
M
AC 230 V
10 A
22 23 24
19 19 21 21
Measured value input
B1
1
Measured value input with LG-Ni 1000 sensor
M
2
Measured value input ground
Signal inputs
D1
3
Signal input
GND
4
Signal ground
D2
5
Signal input
Triac outputs
Y1
6
AC 24 V, 0.5 A switching output
G
7
AC 24 V actuator supply
Y2
8
AC 24 V, 0.5 A switching output
G
9
AC 24 V actuator supply
Room unit
CP–
13
PPS2 ground
CP+
14
PPS2 data
CLA
15
Data A
CLB
16
Data B
L
W
® bus (plug-in)
ON
ORKS
CLA
17
Data A
CLB
18
Data B
Power supply
N
19
Neutral conductor
L
21
Phase line AC 230 V +/- 10 %
Relay outputs
Q13
25
Common feed for Q14, Q24 and Q34
Q14
26
N/O contact AC max. 250 V, 5 (4) A (stage 1)
Q24
27
N/O contact AC max. 250 V, 5 (4) A (stage 2)
Q34
28
N/O contact AC max. 250 V, 5 (4) A (stage 3)
22
Not connected!
Q43
23
Feed for Q44
Q44
24
N/O contact AC max. 250 V, 10 A (electric heating coil)
 Observe the technical data for the relay outputs:
Max. AC 250 V, 5 (4) A and 10 A, respectively
 Local installation regulations must be observed.
Standard RJ45 tool socket for L
1 2 3 4 5 6 7 8
RXC20, RXC21, RXC22 – Room controllers
9
13 14 15 16
2
1
3
4
QAX...
5(4) A
25 26 27 28
W
® devices.
ON
ORKS
1
L
W
®, Data A (CLA)
ON
ORKS
2
L
W
®, Data B (CLB)
ON
ORKS
3
Unoccupied
4
Unoccupied
17 18
LonWorks®
Bus
5
Unoccupied
6
unoccupied
7
PPS2 (CP+)
8
PPS2 (CP–)
CA2N3834en_09
2013-06-16