Honeywell N05 Series Product Data

Non-spring return direct-coupled damper actuators for modulating and floating control

Advertisement

Quick Links

N05, N10 SERIES
NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR
MODULATING AND FLOATING CONTROL
GENERAL
This non-spring return direct-coupled damper actuator
provides modulating and floating/2-position control for:
air dampers,
VAV units,
air handlers,
ventilation flaps,
louvers, and
reliable control for air damper applications with up to 10 sq ft
/ 44 lb-in. (5 Nm) and 20 sq ft / 88 lb-in. (10 Nm) (seal- less
damper blades; air friction-dependent).
FEATURES
Declutch for manual adjustment
Adjustable mechanical end limits
Removable access cover for direct wiring
Mountable in any orientation
Function selection switch for selecting modulating or
floating/2-position control
SPECIFICATIONS
Supply voltage
Nominal voltage
All values stated hereinafter apply to operation under
nominal voltage conditions.
Power consumption
CN7505
CN7510
Control signal
Modulating
Floating/2-Position
Ambient limits
Ambient operating limits
Ambient storage limits
Relative humidity
Safety
Protection standard
Protection class
Overvoltage category
Lifetime
Full strokes
Repositions
Mounting
Round damper shaft
Square damper shaft
Shaft length
min. 1-5/8 in.
End switches (when included)
Rating
Triggering points
Torque rating
Rotation stroke
Dimensions
Weight (without cables)
Noise rating
1
PRODUCT DATA
24 Vac/dc -15%/+20%, 50/60 Hz
24 Vac/dc, 50/60 Hz
5 VA / 2 W
5 VA / 2 W
(0)2...10 Vdc
24 Vac/dc
-5...+140 °F (20...+60 °C)
-22...+176 °F (-30...+80 °C)
5...95%, non-condensing
IP54
II as per EN 60730-1
II
60000
1.5 million
3/8 in...5/8 in.
1/4 in...1/2 in.; 45° steps
Class II
5° / 85°
44 lb-in. (5Nm) / 88 lb-in. (10Nm)
95° + 3°
see "Dimensions" on page 8
1.0 lbs.
35 dB(A) max. at 1 m
63-6233T
CN0B-0545CH33 R0805

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell N05 Series

  • Page 1 N05, N10 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL PRODUCT DATA SPECIFICATIONS Supply voltage 24 Vac/dc -15%/+20%, 50/60 Hz Nominal voltage 24 Vac/dc, 50/60 Hz All values stated hereinafter apply to operation under nominal voltage conditions. Power consumption CN7505 5 VA / 2 W...
  • Page 2: Product Identification System

    N05,N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL Contents of Package The delivery package includes the actuator, parts 1 through 6 PRODUCT IDENTIFICATION SYSTEM (see Fig. 1), plus two cable grommets and a spare cable grommet. C-Electrical Motor RUN MODES N-Fail Safe Function (Non-Spring Return) The function selection switch (see Fig.
  • Page 3 N05,N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL Table 1 describes, for the floating mode, the shaft adapter Table 3 describes, for the modulating mode, the shaft adapter behavior (“stops,” rotates “CCW,” or rotates “CW”) in dependence behavior (“stops,” rotates “totally CCW,” rotates “totally CW,” runs upon the control signals applied to terminals 3 and 4 and upon to “proportional”...
  • Page 4: Manual Adjustment

    N05,N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL Fig 5. Adaption (function selection switch set to 0...10 V) Adaption will be carried out whenever the actuator is in the Fig 3. Final shaft adapter position in dependence upon modulating mode or the floating plus feedback mode or the 2- control signal (example function selection switch setting position plus feedback mode and of 0...10 V)
  • Page 5: Installation

    The internal end switches “A” and “B” are changeover switches NOTE: Further, in order to guarantee IP54, only original which are activated when the shaft adapter moves past a position Honeywell grommets may be used. of 5° and 85°, respectively (see also Table 5). Anti-Rotation Bracket and Screws...
  • Page 6 N05,N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL Wiring Diagrams WIRING To avoid personal injury (electrical shock) and to prevent equipment damage, before wiring, you must remove power. Access Cover IMPORTANT Once the access cover has been removed, please take care to avoid damaging any of the parts now accessible.
  • Page 7 N05,N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL Table 4. Signals at terminals terminal mode modulating floating 2-position 24 V ~/+ (power) unused or (with feedback) unused or (with feedback) 24 V ~/+ (power) 24 V ~/+ (power) common ~/- common ~/- common ~/- 0[2]...10 V (control)
  • Page 8 N05,N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL DIMENSIONS Fig. 2. Dimensions (in in.) Automation and Control Solutions Honeywell International Inc. Honeywell (Tianjin) Limited 1985 Douglas Drive North 66, BaiHe Road, TEDA Golden Valley, MN 55422 Tianjin, 300457,P.R.C. Honeywell Printed in China.

This manual is also suitable for:

N10 series

Table of Contents