7800 SERIES S7830 EXPANDED ANNUNCIATOR
surface area. Wide straps or brackets are preferred
rather than leadwires. Be careful to ensure that
mechanically tightened joints along the ground path,
such as pipe or conduit threads, or surfaces held
together with fasteners, are free of nonconductive
coatings and are protected against corrosion on
mating surfaces.
c. The ControlBus shielded cable, if used, should be
connected to the signal ground terminal 3(c)
provided as a part of the S7830 ControlBus
connector. The shield should be connected at both
ends to earth ground.
5. Recommended Wire Routing:
1
2
3
65-0101—03
Q7800 WIRING SUBBASE
FOR S7830 FIELD HOOKUP
1
L2
2
1
L1
3
(HOT)
MAIN VALVE
PROOF-OF-
CLOSURE
4
BURNER
SWITCH
5
OPERATING
CONTROL
6
AUXILIARY
LIMIT 1
7
AUXILIARY
LIMIT 2
8
LOW WATER
CUTOFF
9
2
HIGH
LIMIT
10
AUXILIARY
LIMIT 3
11
FUEL SELECT
SWITCH
(1/2 OF DPDT)
120V, 50/60Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
IN DUAL FUEL SYSTEMS, 7800 SERIES-T6 CAN BE CONNECTED TO ANY POINT FROM 6 TO 11, INCLUSIVE.
(ANYTHING BEFORE THIS POINT IN CONSIDERED A LIMIT AND ANYTHING AFTER IT IS CONSIDERED AN
INTERLOCK DEVICE SPECIFIC.)
PLACE JUMPERS ON S7800 WIRING SUBBASE ONLY FOR UNUSED CONTROL, LIMIT, OR INTERLOCKS.
Fig. 3. S7830 wiring hookup—dual fuel.
a. Do not run high voltage ignition transformer wires in
the same conduit or in close proximity with the Con-
trolBus wiring.
b. Do not route the ControlBus wires in conduit with
line voltage circuits.
6. Maximum wire lengths:
a. The maximum ControlBus cable length depends on
the number of system modules connected, the noise
conditions and the cable used. The maximum length
of all interconnecting wire is 1000 feet (305 meters).
b. S7830 leadwires: the maximum length of the con-
trol, limit and interlock leadwires is 500 feet (152
meters) to the terminal inputs.
12
HIGH OIL
PRESSURE
13
LOW OIL
PRESSURE
14
HIGH OIL
TEMPERATURE
15
LOW OIL
TEMPERATURE
16
3
17
HIGH GAS
PRESSURE
18
19
AIR FLOW
SWITCH
20
AUXILIARY
INTERLOCK 4
21
AUXILIARY
INTERLOCK 5
22
OIL
20
PRE-
GAS
CONTROL
IGNITION
INTERLOCK
6
ATOMIZING
SWITCH
LOW GAS
PRESSURE
GAS
OIL
FUEL SELECT
SWITCH
(1/2 OF DPDT)
7800
6
7
SERIES
RELAY
LOCKOUT
WIRING
INTERLOCK
2
SUBBASE
TERMINALS
M23113A