Measurement Screen; Menu Structure - ABB CM-UFD.M22 Operating And Installation Instructions

Grid feeding monitoring relay, cm range
Table of Contents

Advertisement

Available languages

Available languages

Designation of the protective functions according to CEI 0-21
Device parameters
Overvoltage >S1
Overvoltage >S2
Undervoltage <S1
Undervoltage <S2
Overfrequency >S1
Overfrequency >S2
Underfrequency <S1
Underfrequency <S2

Measurement screen

The initial screen shows the measured values of the real time line-to-neutral voltages. Use the arrow buttons to switch between the real time
line-to-neutral voltages and the 10-min average line-to-neutral voltages.

Menu structure

The following tables show the submenu structure and configuration possibilities as well as the pre-settings according to
CEI 0-21, which can be loaded in the submenu "General settings" -> "Load settings". Additionally, 5 sets of self-defined pre-settings can
be saved in the memory and loaded by the user.
Submenu: Nominal voltage
Contents of submenu
Measuring principle
Nominal voltage
acc. to CEI 0-21
1st overvoltage med. (59 S1)
2nd overvoltage (59 S2)
1st undervoltage (27 S1)
2nd undervoltage (27 S2)
1st overfrequency (81>S1)
2nd overfrequency (81>S2)
1st underfrequency (81<S1)
2nd underfrequency (81<S2)
Real time line-to-neutral voltages
(L-N)
Configuration possibilities
[3L-N], [3L-L], [1L-N]
[100] - [230.9] V L-N / [173.2] - [400.0] V L-L
10-min average line-to-neutral
voltages (L-N)
Step size
CEI 0-21
3L-N
0.1 V
230 V L-N
10