Product Summary
The ESL Supervised Commercial Wireless Smoke Detector is UL Listed (UL 268) for use in commercial applications. The unit
combines a photoelectric smoke detector with an integrated fixed 135°F temperature and rate-of-rise heat detector, and a
Learn Mode transmitter for use with compatible wireless control panels (see "Specifications" on back page).
Detector Operation
Under normal non-alarm conditions, the detector LED (light-emitting diode) flashes once every nine seconds while monitor-
ing the surrounding conditions. The detector transmits a supervisory signal every 64 minutes indicating its status, which the
panel receives and processes accordingly.
In an alarm condition due to smoke or heat, the LED changes from flashing to on and the built-in sounder emits a temporal 3
pattern (a repeated series of three beeps followed by a short pause). The detector also transmits an alarm signal, which the
panel receives and processes accordingly.
A built-in tamper switch activates whenever the detector is removed from its mounting base, causing the detector to transmit
a tamper signal which the panel receives and processes accordingly.
The detector is powered by two 3-volt lithium batteries (included). When the battery voltage gets low, the detector transmits
a low battery signal which the panel receives and processes accordingly. If the batteries are not replaced within seven days,
the detector's built-in sounder emits a short beep or chirp every 45 seconds.
The detector also includes self-diagnostics, automatically adjusting its sensitivity accordingly to reduce the number of
detector cleanings. When cleaning becomes necessary, the detector has a field-replaceable optical chamber.
General Guidelines
Before mounting detectors, program (learn) them into panel memory and perform a sensor test from the detector's
intended location, to ensure good RF communication to the panel.
Locate the detector in environmentally controlled areas where the temperature range is between 40° and 100°F (4.4° and
37.8°C) and the humidity is between 0 and 90% non-condensing.
Locate detectors away from ventilation sources that can prevent smoke from reaching the detector.
Locate ceiling mounted detectors in the center of the room or hallway, at least 4 inches (10cm) away from any walls or
partitions.
Locate wall mounted detectors so the top of the detector is 4 to 12 inches (10 to 31cm) below the ceiling.
In rooms with sloped, peaked, or gabled ceilings, locate detectors 3 feet (.9 meters) down or away from the highest point
of the ceiling.
When mounting to suspended ceiling tile, the tile must be secured with the appropriate fastener to prevent tile removal.
Note: Do not mount the detector to the metal runners of suspended ceiling grids. The metal runners can draw the magnet's field away
from the detector's reed switch, causing a false tamper alarm
ESL Wireless Smoke Detector
4300 Series
NX Series
Wireless Smoke Detector
Wireless Smoke Alarm/Detector
Temperature
sensor
Test button
Figure 1. Detector Features
LED
Sounder vent
Temperature
sensor
1

Advertisement

Table of Contents
loading

Summary of Contents for GE 60-992-900

  • Page 1: Smoke Detector

    ESL Commercial Wireless Smoke Detector W i r e l e s s 60-992-900 4300 Series NX Series Wireless Smoke Detector Wireless Smoke Alarm/Detector Installation Instructions (PRELIMINARY) Temperature Sounder vent sensor Test button Temperature sensor Figure 1. Detector Features Product Summary The ESL Supervised Commercial Wireless Smoke Detector is UL Listed (UL 268) for use in commercial applications.
  • Page 2 O f f i c e O f f i c e O f f i c e O f f i c e O f f i c e I n c o m m e r c i a l b u i l d i n g s a s m o k e d e t e c t o r C o n f e r e n c e R o o m s h o u l d b e l o c a t e d i n e a c h r o o m .
  • Page 3: Locations To Avoid

    Locations to Avoid Do not install smoke detectors: • in or near areas where combustion particles are normally present such as in kitchens, garages, near furnaces, hot water heaters, or gas space heaters. • on the ceiling in rooms next to kitchens where there is no transom between the kitchen and such rooms. •...
  • Page 4: Sensor Test

    Alignment arrow Alignment tab Battery compartment Figure 3 - Battery Compartment Figure 4 - Detector-to-Base Alignment Figure 5. Removing Detector Cap Mounting Mount the detector with the appropriate fasteners. Mounting hardware is included (screws and anchors), however you may need different hardware depending on the installation. Separate the detector from the mounting base by turning the detector counter clockwise about 15 degrees.
  • Page 5: Troubleshooting

    Sensitivity Test Use this test to check detector sensitivity. Press and hold the detector test button for two seconds, then release it. The detector transmits a test signal, then performs a self-test that causes the LED to flash 1 to 9 times. Count the number of LED flashes, then use the following table to determine if any action is necessary.
  • Page 6: Maintaining The Detector

    7. Line the new field replaceable optical chamber up with the optical base and snap into place both sides of the optical chamber. 8. Replace the detector cap as follows: -Line the detector cap up with the smoke detector. Optical base Optical -Insert the detector cap into the smoke detector and...
  • Page 7: Limited Warranty

    Limited Warranty ESL is a brand of GE Interlogix. The manufacturer warrants this smoke detector (except batteries) to be free from defects in material and workmanship under conditions of normal use for a term of 3 years from the date of manufacture.
  • Page 8: Specifications

    Tualatin, OR 97062 North St. Paul, MN 55109 Phone: 503-692-4052 www.GE-InterlogixSecurity.com USA & Canada: 800-547-2556 Phone: 651-777-2690 Technical Service: 800-648-7424 USA & Canada: 800-777-5484 © 2004 GE Security FaxBack: 800-483-2495 Technical Service: 800-777-2624 1039XXX-Rev. PRELIMINARY 09/04 ESL Wireless Smoke Detector...

Table of Contents