Cbu Preparation - ABB ACS 6000 Commissioning Manual

Medium voltage ac drive
Hide thumbs Also See for ACS 6000:
Table of Contents

Advertisement

Chapter 6 - Insulation Resistance Measurement
6.2.3

CBU Preparation

32 (of 62)
The following preparatory measures must be taken in a Capacitor Bank
Unit (CBU):
3
Short circuit of DC link busbars is already made in TEU.
1
Make a short circuit between the auxiliary contacts of the earthing
isolator and connect it to ground (-X715 / 9,10).
Note that the earthing isolator must be in position "NOT EARTHED".
2
Short circuit and ground the coil of the charging relay K2CHU
(-X714 / 1,2)
3
Ground the primary side of the charging transformer TCHU
(-X710 / 7)
4
Connect the secondary side of the charging transformer TCHU to
the DC link and short circuit the charging diode bridge.
5
Short circuit the common mode filter capacitor CGND.
6
Disconnect the common mode filter capacitor CGND from PE
(protective earth).
7
Disconnect the HV-line from the coupling unit AGH520S, if included
in the converter configuration.
3BHS135824 ZAB E01Rev. D
2
4
6
PGND
ACS 6000 Commissioning Manual
DC_plus
DC_NP
5
DC_minus
ABB