(2) Current diagnostic information non-notification time area (Un\G2085)
3
- 37
3.4 Buffer Memory
3.4.6 Diagnostic information area
This area stores the remaining time during which no diagnostic information is notified
after communication start (after Data exchange start completed signal (X00) turns
ON). (initial value: 0 seconds)
The non-notification time is set in the Diagnostic information non-notification time
setting area (Un\G2084).
Table3.16 Current diagnostic Information Non-notification Time Area (Un\G2085)
Stored Value
0 to 65535
When the time set in the Diagnostic information non-notification time setting area
(Un\G2084) has elapsed after communication start (after Data exchange start completed
signal (X00) turns ON), the value in the Current diagnostic information non-notification
time area (Un\G2085) becomes 0.
While communication is stopped (Data exchange start request signal (Y00): OFF), the
remaining time is held until the Data exchange start request signal (Y00) is turned ON
again.
A countdown time (remaining time), during which no diagnostic information
is notified, is stored. (Unit: seconds)
No diagnostic information is notified until the value reaches 0.