Dimensional Drawings - Honeywell LKS 131 Product Handbook

For air dampers on single, dual stage and modulating burners

Advertisement

Direction of rotation
see "Type overview"
Torque and holding torque
see "Type overview"
Drive times
5, 15, 38 sec. for 90°
Limit and auxiliary switches
max. 7
operation with adjustable cam discs, cams coloured in
normal way:
blue
fully closed position
orange
low load
red
high load
black
spare switches for additional functions
switching voltage
AC 24....230 V
switching capacity
with inductive loads 250 VA
DIMENSIONAL DRAWING
D) Fixing hole
through-hole 5,3 mm inside dia
EN2C-0111SZ20 R0202
Ambient temperature
operation
transport and storage
Condensation, icing and exposure to water not
permitted
Weight
• approx. 500 g
8,5
47
60
4
0 ... +60° C
-20 ... +60° C
A
cable output
100
14
1

Advertisement