Venting (cont'd)
CUTTING
OPENING
THROUGH
AN OUTSIDE
WALL AND COLLAR
INSTALLATION
After reading the manual and you have determined the location
of the opening in the wall, (using the drawing below), cut a 3½"
hole through an exterior wall.
NOTE: When determining location of the opening in the
outside wall allow for the ¼" rise per foot that has taken
place in the horizontal run.
CONNECTING
PVC, ABS OR CPVC PIPE VENT TO
BLOWER
"
40
1. The manufacturer
has supphed a 3 PVC or ABS Schedule
street elbow for connection
to the water heater when turning
immediately
horizontally
off the blower• Place the elbow in
the required direction on the blower and usinl_ 3 sheet metal
screws, attach the elbow. If using a galvanized elbow attach-
ment is the same.
CL of Flue--_ .......
_
"_[_t
?-
40 gal.-60"
50 Gal.- 59½"
_r
The Y' PVC Schedule
40 vent pipe can be run from the water
heater
through
the wall or from the wall to the water heater,
whichever
is most
convenient.
The vent pipe must extend
a
minimum
of 1½" through
the exterior wall. Extending
the vent
cap as far as possible from the surface of the exterior wall will
help minimize
discoloration
of the wall in this area which may
be caused by the flue gases. Note that the inside
collar must be
slipped over the vent piping before locating the pipe through the
wall. Before securin_
the inside and outside collars to the wall,
use a silicone sealer between
pipe and opening to insure a water
and air tight seal.
I
I
2. If there is to be a vertical run of vent from the blower, the 3"
PVC, ABS or galvanized pipe must be attached to the blower
using 3 sheet metal screws. If using galvanized piping attach-
ment is the same. Additionally, you must seal all joints using a
suitable silicone sealer such as GE RTV-103 or equivalent.
INSTALLATION
SHOWING USE OF PVC, ABS OR
CPVC PIPE
SILICONE_
SEALER
SCREW
__ 1 +h" MIN.EXTENSION
THROUGH
EXTERIOR
WALL
SEALER
SCREEN
VENT CAP MUST BE
_
POSITIONED
DOWNWARD
18